5.3
Levelling the boiler
The boiler must be level to prevent air pockets forming
inside the boiler and to ensure that the condensate can
freely drain from the condensate pan.
NOTICE: Boiler damage through insufficient
load-bearing capacity of the installation area
or unsuitable substrate!
B Ensure that the installation area offers
sufficient load-bearing capacity.
B Bring the boiler into its final position.
B Level the boiler horizontally by means of the adjustable
feet [1] and a spirit level [2].
Fig. 8
Levelling the boiler
1
Adjustable feet
2
Spirit level
Logano plus GB312 - Subject to technical modifications.
5.4
Flue and ventilation air connections
5.4.1
Making the flue connection
When installing the flue connection, observe the
following:
• Country-specific regulations.
• The flue pipe cross-section must comply with all
current regulations.
• Select the shortest possible route for the flue pipe.
• Lay the flue pipes so that they slope upwards.
DANGER: Risk to life from escaping flue gas
inside the installation room!
B Gaskets in the flue connections must be
present, in perfect condition and correctly
inserted.
B Insert the boiler connection elbow (accessory) into the
flue connection.
B Make the flue connection in accordance with the
requirements applicable in your country.
Fig. 9
Fitting the flue connection
1
Boiler connection elbow (accessory)
2
Boiler connector (accessory)
5
Installation