10
Troubleshooting
Display
Fault
1)
Type
code
code
V
9Y
500
501
502
503
V
CY
566
V
CY
567
V
CO
568
V
CO
569
Tab. 28 Fault displays
1) V = locking; B = blocking
66
Cause
Description
Internal SAFe
Internal SAFe
relay faulty.
electronics faulty.
Return
The control unit
temperature
receives unrealistic
values from the
< -5 °C
return temperature
(interruption)
sensor.
Return
The control unit
temperature
receives unrealistic
values from the
> 130 °C
return temperature
(short circuit)
sensor.
Water
Water pressure
pressure
sensor interruption
sensor fault
(voltage > 3.5 V).
(cable break).
Water
Water pressure
pressure
sensor short
sensor fault
circuit
(short circuit).
(voltage < 0.5 V).
Test procedure/cause
Press "Reset" and wait to
see if the fault has been
removed.
Check the lead between
the SAFe and the return
temperature sensor.
Check electrical
connection of the SAFe
cable.
Check resistance values of
temperature sensor
according to table.
Check voltage at the
temperature sensor
terminals inside the SAFe
according to table.
Check the lead between
the SAFe and the return
temperature sensor.
Check electrical
connection of the SAFe
cable.
Check resistance values of
temperature sensor
according to table.
Check voltage at the
temperature sensor
terminals inside the SAFe
according to table.
Check lead to water
pressure sensor.
Check water pressure
sensor.
Check lead to water
pressure sensor.
Check water pressure
sensor.
Logano plus GB312 - Subject to technical modifications.
Action
Replace the SAFe if the
fault persists after
"Reset" has been
pressed.
Replace cable if
required.
Remedy contact
problem if required.
Replace temperature
sensor if required.
Replace SAFe if
resistance values of the
temperature sensor are
correct, but voltage
values are incorrect.
Replace cable if
required.
Remedy contact
problem if required.
Replace temperature
sensor if required.
Replace SAFe if
resistance values of the
temperature sensor are
correct, but voltage
values are incorrect.
Remedy any
interruption.
Replace water pressure
sensor.
Remedy any short
circuit.
Replace water pressure
sensor.