I/O Module Installation and Wiring - I/O Module Installation Procedures
Step
5
If installing High Level 16 channel Analog Input module, set its SW1 and SW2 DIP switches to
ON. This connects an internal 250 ohm resistor.
A small slotted screwdriver or paperclip works well; avoid using pencils.
6
If installing 8- or 16-channel Analog Output module, set its DIP switch as follows. (Switch is
located at edge of module, marked "SW1".)
•
For internal rack power, set DIP switch to ON.
•
For external power (18-36V), set DIP switch to OFF (default).
Note: 24VDC external power is required if using 6 or more 8-pt. AO modules or 3 or more 16-pt.
AO modules.
A small slotted screwdriver or paperclip works well; avoid using pencils.
Revision 19
06/14
Procedure
HC900 Process Controller Installation and User Guide
Comments
Reference
77