Appendix - Installation of Remote Termination Panels (RTPs) - Analog Input/Digital Input/Digital Output/Analog
Output
16 Point Analog Output
Step
1
ATTENTION: RTP and cables are intended for permanent installation within their own enclosure.
Mount RTP cable assembly to HC900 Controller (Figure 92).
Remove appropriate key tabs from terminal board to allow mating with the module. See page 75.
Connect terminal block end of desired cable assembly to 16 point Analog Output module at
controller. Choose from:
900RTC-3210
900RTC-3225
900RTC-3250
Install 16 point Analog Output label into the module connector cover.
Connect both shield drain wires to the grounding bars at the base of the HC900 rack. All field-wiring
shields must be grounded as described in the shield grounding section (page 70).
2
Mount RTPs to DIN rail.
Latch to rail. See page 244.
Connect cables to RTPs. Cables are marked "RTP A" and "RTP B." In step 4, RTP A will be wired to
Inputs 1-10, RTP B to Inputs 9-16. You can write on the RTPs' labels to distinguish them.
Note: Inputs 9 and 10 are wired between both RTPs.
3
Set/verify jumper positions on each RTP as shown.
Module Removal / Insertion Under Power (RIUP) is supported by turning off Switch SW1 to allow removal of
the module from the rack without causing an arc. See page 73.
ATTENTION: SW1 opens the + side of the External 24V Power so that RIUP of module is possible.
See page 233 for RTP internal schematic.
234
Remote Terminal Cable assembly, 1.0 meters long
Remote Terminal Cable assembly, 2.5 meters long
Remote Terminal Cable assembly, 5.0 meters long
HC900 Process Controller Installation and User Guide
Action
Jumper open
Jumper closed
Revision 19
06/14