I/O Module Installation and Wiring - I/O Terminal Block Wiring Diagrams
NOTE
When exceeding 1.0 A per output, it is recommended (but not required) to connect the high-
current loads to every other output - for example, outputs 1, 3, 5, 7 or 2, 4, 6, 8. This distributes
heat more evenly across the heat sink.
Jumper Comb
A ten-position jumper comb is available for inter-connecting all L1 (Hot) terminals (1, 3, 5, 7, 9, 11, 13, 15,
17, 19). See Figure 60.
Replaceable Fuses
Each output circuit on the AC Output Module includes a (plug-in) replaceable fuse.
Replacement fuse is from Wickmann, part #3741315041. This is a 3.15 Amp time lag fuse with UL/CSA
approval for 250 VAC.
Hazardous voltages exist at terminal blocks.
Using switches at field devices disconnect the field wiring from power sources before servicing.
Failure to comply with these instructions could result in death or serious injury.
106
HC900 Process Controller Installation and User Guide