Appendix - Installation of Remote Termination Panels (RTPs) - Analog Input/Digital Input/Digital Output/Analog
Output
16 Point Contact Digital Input
Step
1
ATTENTION: RTP and cables are intended for permanent installation within their own enclosure.
Mount RTP cable assembly to HC900 Controller (Figure 92).
Remove appropriate key tabs from terminal board to allow mating with the module. See page 75.
Connect desired cable to 16 point Contact DI module at controller. Choose from:
900RTC-L010
900RTC-L025
900RTC-L050
Install 16 point contact DI module label into the module connector cover.
Connect shield drain wire to the grounding bars at the base of the HC900 rack. All field-wiring
shields must be grounded as described in the shield grounding section (page 70).
2
Mount RTP to DIN rail.
Latch to rail. See page 244.
Connect cable to RTP
3
Set jumper positions as shown for the 16 point contact digital input module.
SW1 is not used. Module RIUP is not affected by using the RTP.
See page 230 for RTP internal schematic.
Revision 19
06/14
Remote Terminal Low Voltage Cable Assembly, 1.0 meters long
Remote Terminal Low Voltage Cable Assembly, 2.5 meters long
Remote Terminal Low Voltage Cable Assembly, 5.0 meters long
HC900 Process Controller Installation and User Guide
Action
Jumper open
Jumper closed
221