Specifications - General Specifications
12 I/O slot chassis with
redundant power
support
Redundant CPU rack
I/O Wiring
Type
Terminal Block Styles
Gauge wires
Shield terminals
Power (P01)
Voltage
In Rush Current
Input rating
Output rating
Fuse
Power (P02)
Voltage
In Rush Current
Input rating
Output rating
Fuse
Power (P24)
Voltage
In Rush Current
Input rating
Output rating
Fuse
Normal Scan Time
Fast Scan Time
Detection+Failover
Time from Lead to
Reserve CPU
Run-Mode Edit
Transfer Time
Operating Modes
Revision 19
06/14
C30
5.4"(137mm) H x 26.9"(683.3mm) W x 6.0"
to 6.9" (175.3mm)
N/A
* 6.4 (162.6) for 32 DI/DO and 16 AI Modules
Removable terminal blocks
20 screw: Barrier or Euro-style, tin-plated or gold-plated (for DC connections)
36 screw: Euro style gold plated (Required with certain higher capacity modules)
20 screw:
Barrier style – #14 to 26 AWG, solid or stranded
Euro-style - #14 to 26 AWG, solid or stranded
36-screw:
Euro-style - #12 to 26 AWG, solid or stranded
Optional brackets mounted top/bottom of rack
Universal power, 90 to 264VAC, 47 to 63 Hz
7 Amps peak-to-peak for 150 ms at 240VAC
130 VA
60W
Internal non-replaceable fuse. User installed external fuse.
Universal power, 90 to 264VAC, 47 to 63 Hz
7 Amps peak-to-peak for 120 ms at 240VAC
90 VA
28W
Internal non-replaceable fuse. User installed external fuse.
21 to 29VDC
30A for 3ms @29VDC
72.5W
60W
Internal non-replaceable fuse. User installed external fuse.
500ms. Each analog input card has its own A/D converter providing parallel processing.
53ms for up to~250 fast
27ms for up to ~250 fast
logic blocks
logic blocks
67ms for up to ~315
53ms for up to~500 fast
fast logic blocks
logic blocks
107ms for up to ~400
67ms for up to ~780 fast
fast logic blocks
logic blocks
107ms for up to ~1040
fast logic blocks
133ms for up to ~1300
fast logic blocks
N/A
3 normal scan times (1.5 sec. typical) for all configuration edits not including I/O changes
Run (No configuration download in this position)
Run/Program (Download allowed)
Program (Outputs Off, initialization on download).
Offline mode is available via software selection (for AI calibration).
HC900 Process Controller Installation and User Guide
C50
C70
*
(151.7mm) D (rear mounting plate extends height
27ms for up to ~330 fast
logic blocks
53ms for up to~660 fast
logic blocks
67ms for up to ~1040
fast logic blocks
107ms for up to ~1380
fast logic blocks
133ms for up to ~1700
fast logic blocks
267ms for up to~3300
fast logic blocks
C75
5.4"(137mm) H x
10.3"(261.6mm) W x
*
6.0,,"
(151.7mm) D
(rear mounting plate
extends height to 6.9"
(175.3mm)
53ms for up to~500 fast
logic blocks
67ms for up to ~780 fast
logic blocks
107ms for up to ~1040
fast logic blocks
133ms for up to ~1300
fast logic blocks
267ms for up to~2500
fast logic blocks
Up to 4 analog scan
cycles
195