Heat & Glo RED60 Installation Manual page 35

Installation and appliance setup
Hide thumbs Also See for RED60:
Table of Contents

Advertisement

Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles between ceiling fi restops.
• ALWAYS maintain specifi ed clearances around venting and fi restop systems.
• Install wall shield and ceiling fi restops as specifi ed.
Failure to keep insulation or other material away from vent pipe may cause fi re.
PVK-80 Top Vent - Horizontal Termination
Venting with 1 elbow
V
Minimum
V
1
1
2 ft.
610 mm
30 ft.
3 ft.
914 mm
40 ft.
4 ft.
1.2 m
50 ft.
V
+ H
= 50 ft. (15.2 m) Maximum
1
1
Figure 4.48
+ H
Maximum
1
9.1 m
12.1 m
15.2 m
H
1
Heat & Glo • RED60 Installation Manual • 2159-980 Rev. D • 11/13
WARNING
Note: Must have 24 inches minimum
vertical vent prior to attaching any
elbow to the appliance.
V
Note: Use DVP Series
components only.
1
35