AMAX 2100 / 3000 / 4000
RPS cannot perform remote
programming and control
Occasionally abnormal
communication in use of
Contact ID/personal
telephone alarm
No response from the keypad
and the alarm siren
(disabled) when an alarm is
triggered by the zone
The AMAX panel cannot send
any reports (programmed to
send reports to receiver)
A-LINK cannot be connected
with ITS- DX4020-G
Bosch Sicherheitsysteme GmbH
–
Both addresses 0144
and 0145 are set to 0
–
Extension system is used
in the telephone network
–
The telephone network
support ADSL as well
–
The zone silent alarm is
enabled
–
The transmission format
of the receiver is
programmed to 0 = not
used
–
The parameters of ITS-
DX4020-G are not
properly set.
Installation Guide
Troubleshooting | en
–
Program the address
0144 to a number from 1
to 15. Program the
address 0145 to 1
–
Add dial delay in
programming
–
Connect the system after
the ADSL filter
–
Disable the zone silent
alarm
–
Program the
transmission format of
the receiver to 1 or 3
–
Recommend to set the
parameter ACK TIMEOUT
of ITS-DX4020-G to the
maximum (600) and set
TRANSMIT BUFFER LIFE
TIME to the maximum
(120)
2014.11 | 02 | F.01U.267.112
139