24
Mantel Requirements
•
The optional mantel must be a minimum 23" above the top of the faceplate (61" above the
base). See Figure 29.
•
The mantel must not extend more than 8-1/2" in front of the faceplate.
•
Mantel side columns that extend more than 3/4" beyond the faceplate must maintain an 18"
clearance to the faceplate.
Minimum
Mantel
Clearance
8" Min.
© Travis Industries
Installation
(for qualified installers only)
23"
Mantel (may be
combustible)
4050714
Minimum
Hearth
Width = 60"
20" (18" in
some cases)
Figure 29
93508093