Chimney Termination Requirements

The chimney must terminate a minimum 3' above the roof and 2' above any portion within 10'
(measured horizontally – see Figure 26). This applies to flat and sloped roofs.
The chimney must have a chimney cap. A spark arrestor may be required in your area (check
with the local building department).
When using a chase to enclose a chimney, the chimney termination is not required to be 3'
above the chase as long as the chase is above the roof structure. The chimney cap must still
maintain the 2, 3, 10 clearance to any other structure. See the illustration below.
Chimneys extending beyond a certain height (frequently 5') above the roof may require braces
(check the instructions included with the chimney for details)
Slanted Roofs
Chimney must
extend 3'
above the roof
Flat Roofs
Chimney must
extend 3'
above the roof
Chase Installations
© Travis Industries
Installation
6" Min.
(for qualified installers only)
Chimney must extend 2'
above any portion of the roof
within 10' of the chimney
Chimney must extend 2'
above any portion of the roof
within 10' of the chimney
Cap
Storm Collar
Drip Collar (seal around edges)
Sheet Metal Chase Top
Chimney Pipe
Chase
4050714
21
Figure 26
93508093