15.4 Environmental Specifications
Operating Temperature
Operating Altitude
Storage Temperature
Relative Humidity (operating and
storage)
Acoustical Noise
EMI Suppression
Electrostatic Discharge (ESD)
Immunity
Powerware BPIV (10 kVA- -30 kVA) Installation and Operation
164201406 Rev. C 013004
0 to 40˚C without derating. The recommended
operating temperature is 25˚C.
Maximum 1500m (5000 ft) at 40_C without
derating
---20 to +70˚C (prolonged storage above 40˚C
will cause rapid battery self-discharge)
95% maximum, noncondensing
60 dBA at a 1m distance (Typical)
Meets FCC Regulation 47, Part 15, for class A
devices
Meets IEC 801---2 specifications. Withstands up
to 25 kV pulse without damage and with no
disturbance or adverse effect to the critical load.
15--3