Product Specifications; Model Numbers; Ups System Input - Powerware BPIV Installation & Operation Manual

10–15 kva/20–30 kva
Table of Contents

Advertisement

Product Specifications

15.1 Model Numbers

The UPS systems are housed in freestanding, cabinets with safety shields behind
the front panels. The UPS systems are available in 50/60 Hz with various output
power ratings. Smaller models within a system may be upgraded in the field to
larger models:
System
Powerware BPIV–15
Powerware BPIV–30
The following sections detail the input, output, environmental, and battery specifications for
the UPS.

15.2 UPS System Input

Operating Input
Voltage
(Nominal +10/-- 15%)
Operating Input
Frequency Range
Operating Input
Current
Battery Charge
Current
Input Current
Harmonic Content
Power Factor
Line Surges
Battery Voltage
Powerware BPIV (10 kVA- -30 kVA) Installation and Operation
164201406 Rev. C 013004
Models
10 and 15 kVA
20 and 30 kVA
600 VAC for operation from 510 VAC to 660 VAC (50/60 Hz)
480 VAC for operation from 408 VAC to 528 VAC (50/60 Hz)
208 VAC for operation from 177 VAC to 229 VAC (50/60 Hz)
3 Hz of nominal (50 Hz or 60 Hz)
Refer to Appendix A, Tables A through E, for 10, and 15 kVA
Models and Tables G through K, for 20, 25, and 35 kVA
Models.
Reduced for Generator:
Adjustable
Battery Charge:
Up to 7 Amperes for 10, and 15 kVA models
Up to 14 Amperes for 20, 25, and 30 kVA models
10% THD at full load (with input filter option installed)
30% THD at full load (without input filter option installed)
Minimum 0.96
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801---4
288 VDC nominal
(144 cells @2V/cell)
15
Nominal Frequency
50/60 Hz
50/60 Hz
15--1