Powerware BPIV Installation & Operation Manual page 187

10–15 kva/20–30 kva
Table of Contents

Advertisement

Table Q. Power Cable Conduit Requirements Powerware BPIV (20 kVA -- 30 kVA)
Powerware
System
BPIV ---30/20
BPIV ---30/20
BPIV ---30/20
BPIV ---30/20
BPIV ---30/25
BPIV ---30/25
BPIV ---30/25
BPIV ---30/25
Powerware BPIV (10 kVA- -30 kVA) Installation and Operation
164201406 Rev. C 013004
Voltage
Terminal
AC Input to UPS
(A, B, C, Gnd)
208
AC Input to Bypass
(A, B, C, Neut, Gnd)
AC
AC
Output
(A, B, C, Neut, Gnd)
AC Input to UPS
(A, B, C, Gnd)
AC Input to Bypass
480
AC
C
(A, B, C, Neut, Gnd)
Output
(A, B, C, Neut, Gnd)
AC Input to UPS
(A, B, C, Gnd)
AC Input to Bypass
600
(A, B, C, Neut, Gnd)
AC
C
Output
(A, B, C, Neut, Gnd)
288
External Battery DC Source
DC
(Positive, Negative, Gnd)
AC Input to UPS
(A, B, C, Gnd)
AC Input to Bypass
208
AC
C
(A, B, C, Neut, Gnd)
Output
(A, B, C, Neut, Gnd)
AC Input to UPS
(A, B, C, Gnd)
AC Input to Bypass
480
(A, B, C, Neut, Gnd)
AC
C
Output
(A, B, C, Neut, Gnd)
AC Input to UPS
(A, B, C, Gnd)
600
AC Input to Bypass
(A, B, C, Neut, Gnd)
AC
C
Output
(A, B, C, Neut, Gnd)
288
External Battery DC Source
DC
(Positive, Negative, Gnd)
Number of
Wires in
Conduit
4
5
5
4
5
5
4
5
N/A
3
4
5
5
4
5
5
4
5
N/A
3
DESCRIPTION:
POWER WIRING INSTALLATION NOTES
DRAWING NO:
164201406---1
REVISION: C
Minimum
Conduit
Number of
Trade Size
Conduits
(inches)
1-1/4
1
1-1/4
1
1-1/4
1
3/4
1
3/4
1
3/4
1
1/2
1
1/2
1
N/A
N/A
1
1
1-1/4
1
1-1/4
1
1-1/4
1
3/4
1
3/4
1
3/4
1
1
3/4
1
3/4
N/A
N/A
1
1
SHEET:
12 of 14
DATE:
013004
A ---13