Powerware BPIV 30 kVA Installation & Operation Manual

Parallel cabinet 15 kva and 30 kva
Table of Contents

Advertisement

Quick Links

BPIV
Parallel Cabinet
15 kVA and 30 kVA
INSTALLATION & OPERATION MANUAL

Advertisement

Table of Contents
loading

Summary of Contents for Powerware BPIV 30 kVA

  • Page 1 BPIV Parallel Cabinet 15 kVA and 30 kVA INSTALLATION & OPERATION MANUAL...
  • Page 3 BPIV Parallel Cabinet 15 kVA and 30 kVA INSTALLATION & OPERATION MANUAL www.powerware.com...
  • Page 4: Save These Instructions

    Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at their own expense. Powerware BPIV Parallel Cabinet Installation and Operation 164201409 REV. B 101503...
  • Page 5: Table Of Contents

    ......... . 3---6 Powerware BPIV Parallel Cabinet Installation and Operation 164201409 REV. B...
  • Page 6 ..........W ---1 Powerware BPIV Parallel Cabinet Installation and Operation 164201409 REV. B...
  • Page 7 Path of Current Through the Parallel System in Battery Mode . . . 3---6 Figure 4---1. BPIV 15 kVA and 30 kVA Parallel Cabinet Indicators ... . 4---3 Powerware BPIV Parallel Cabinet Installation and Operation 164201409 REV. B 101503...
  • Page 8 This Page Intentionally Left Blank. Powerware BPIV Parallel Cabinet Installation and Operation 164201409 REV. B 101503...
  • Page 9: Introduction

    Introduction The Powerware BPIV Parallel System can be utilized to prevent loss of valuable electronic information, minimize equipment downtime, and/or minimize the adverse effect on equipment and production due to unexpected power problems. The Powerware BPIV Parallel System continually monitors incoming electrical power and removes the surges, spikes, sags, and other irregularities that are inherent in commercial utility power.
  • Page 10: Basic System Configurations

    Each component of your Parallel System is housed in a free-standing cabinet. The cabinets line up and match in style and color, and have safety shields behind the doors for hazardous voltage protection. The following illustration depicts the Powerware BPIV Parallel Cabinet.
  • Page 11: Using This Manual

    UPMs to ensure trouble-free operation. In particular, you should be thoroughly familiar with the Remote Emergency Power Off procedure described in the Powerware BPIV UPS Installation and Operation manual referenced at the end of this section.
  • Page 12: Conventions Used In This Manual

    • Ensure the area around the Parallel System is clean and uncluttered. • Observe all DANGER, CAUTION, and WARNING notices affixed to the inside and outside of the equipment. Powerware BPIV Parallel Cabinet Installation and Operation 164201409 REV. B 101503...
  • Page 13: For More Information

    Also described are the communications capabilities of the UPS system and remote notification. Contact your local Powerware Field Service office for information on how to obtain copies of this manual. Getting Help If you need to schedule initial startup, need regional locations and telephone numbers,...
  • Page 14 This Page Intentionally Left Blank. Powerware BPIV Parallel Cabinet Installation and Operation 164201409 REV. B 101503...
  • Page 15: Section I

    Section I Installation Powerware BPIV Parallel Cabinet Installation and Operation 164201409 REV. B 101503...
  • Page 16 This Page Intentionally Left Blank. Powerware BPIV Parallel Cabinet Installation and Operation 164201409 REV. B 101503...
  • Page 17: Getting Started

    The operating environment must meet the weight, airflow, size and clearance, requirements specified in Appendix A. Powerware BPIV Parallel Cabinet Installation and Operation 1--1 164201409 REV. B 101503...
  • Page 18: Environment Considerations

    For external wiring requirements, including the minimum AWG size of external wiring, refer to Tables A through E in Appendix A for the Powerware BPIV 15 kVA Parallel Cabinet or Tables F through J in Appendix A for the Powerware BPIV 30 kVA Parallel Cabinet.
  • Page 19: Inspecting And Unpacking The Cabinet

    Use a forklift or other material handling equipment to move the cabinet to a convenient unpacking area. Insert the forklift jacks between the pallet supports on the bottom of the unit. Powerware BPIV Parallel Cabinet Installation and Operation 1--3 164201409 REV. B...
  • Page 20 After removing the protective covering, inspect the contents for any evidence of physical damage, and compare each item with the Bill of Lading. If damage has occurred or shortages are evident, contact the Powerware Customer Service Department immediately to determine the extent of the damage and its impact upon further installation.
  • Page 21: Installing The Parallel System

    Drawing 164201409---2 and Table Q in Appendix A identify the control wiring terminations. UPM Cabinet Installation To install the UPMs, refer to the Powerware BPIV UPS Installation and Operation manual referenced in the Introduction to this manual. Powerware BPIV Parallel Cabinet Installation and Operation 2--1 164201409 REV.
  • Page 22: Parallel Cabinet Installation

    To install a Parallel Cabinet, perform the procedures in the following paragraphs. 2.3.1 Unloading the Powerware BPIV Parallel Cabinet from the Pallet The Parallel Cabinet is bolted to a wooden pallet supported by wood skids. To remove the pallet, perform the following procedure: WARNING: The Parallel Cabinet is heavy.
  • Page 23 VENTED FRONT PANEL SHIPPING PALLET BOLTS (2) SHIPPING BOLTS (1) FRONT SHIPPING BRACKET (3) FRONT VIEW Figure 2 ---1. Removing Front Shipping Bracket --- Powerware BPIV Parallel Cabinet Powerware BPIV Parallel Cabinet Installation and Operation 2--3 164201409 REV. B 101503...
  • Page 24 REMOVABLE SKID (5) SHIPPING BOLTS (1) PALLET REAR SHIPPING BRACKET (3) SHIPPING BOLTS (2) REAR VIEW Figure 2 ---2. Removing Rear Shipping Bracket --- Powerware BPIV Parallel Cabinet Powerware BPIV Parallel Cabinet Installation and Operation 2--4 164201409 REV. B 101503...
  • Page 25: Installing Parallel Cabinet External Power Wiring

    2.3.2. 2.3.2 Installing Parallel Cabinet External Power Wiring Remove front vented panel from the Powerware BPIV Parallel Cabinet. Front panel is secured with magnetic latches and is removed by pulling panel straight forward to disengage magnetic latches (see Figure 2---1).
  • Page 26 Locate CAN and Building Alarm 4 terminals by referring to drawings 164201409---2 and 164201409---6 in Appendix A of this manual. For connections to the UPMs, refer to Chapter 2 and Appendix A in the Powerware BPIV UPS Installation and Operation manual referenced in the Introduction to this manual.
  • Page 27: Initial Startup

    Installation Checklist to be sure you have completed all applicable equipment installation. NOTE: The Installation Checklist MUST be completed prior to starting the Parallel System for the first time. Powerware BPIV Parallel Cabinet Installation and Operation 2--7 164201409 REV. B 101503...
  • Page 28: Installation Checklist

    A 120VAC service outlet is located within 25 feet of the UPMs and Parallel equipment. Building alarms are wired appropriately. Startup and operational checks performed by authorized service personnel. Powerware BPIV Parallel Cabinet Installation and Operation 2--8 164201409 REV. B...
  • Page 29 Notes ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ Powerware BPIV Parallel Cabinet Installation and Operation 2--9 164201409 REV. B 101503...
  • Page 30 This Page Intentionally Left Blank. Powerware BPIV Parallel Cabinet Installation and Operation 2--10 164201409 REV. B 101503...
  • Page 31: Operation

    Section II Operation Powerware BPIV Parallel Cabinet Installation and Operation 164201409 REV. B 101503...
  • Page 32 This Page Intentionally Left Blank. Powerware BPIV Parallel Cabinet Installation and Operation 164201409 REV. B 101503...
  • Page 33: Understanding Parallel System Operation

    System Operation Looking Inside the Parallel System The Parallel Cabinet extends the normal operation of the Powerware BPIV UPS units by offering parallel capacity/redundant capability. The Parallel system continues to maintain power to the critical loads during commercial electrical power brownout, blackout, overvoltage, undervoltage, and out-of-tolerance frequency conditions.
  • Page 34: Normal, Battery, And Bypass Modes With Parallel Operation

    UPMs ensures that operating mode changes are automatic and transparent to the critical load. The following descriptions provide the differences in Parallel System operating modes. Powerware BPIV Parallel Cabinet Installation and Operation 3--2 164201409 REV. B 101503...
  • Page 35: Normal Mode

    If the UPMs become overloaded or unavailable, the Parallel System switches to Bypass mode. The Parallel System automatically returns to Normal mode when the overload condition is cleared and system operation is restored within specified limits. Powerware BPIV Parallel Cabinet Installation and Operation 3--3 164201409 REV. B 101503...
  • Page 36: Bypass Mode

    Figure 3 ---2. Path of Current Through the Parallel System in Bypass Mode CAUTION: The critical load is not protected while the Parallel Cabinet is in Bypass mode. Powerware BPIV Parallel Cabinet Installation and Operation 3--4 164201409 REV. B 101503...
  • Page 37 Bypass mode is a normal operating mode, and not an alarm condition. However, if the Parallel System is unable to return to Normal mode following an automatic transfer to Bypass mode, an alarm condition is recorded. Powerware BPIV Parallel Cabinet Installation and Operation 3--5 164201409 REV. B...
  • Page 38: Battery Mode

    The UPMs will remain in this operating mode until the input power to the rectifier is again within the specified voltage or frequency acceptance windows. Powerware BPIV Parallel Cabinet Installation and Operation 3--6 164201409 REV. B...
  • Page 39 The greater the load, the less support time the battery will have. Decrease the load, and the battery support time will generally increase. Powerware BPIV Parallel Cabinet Installation and Operation 3--7 164201409 REV. B 101503...
  • Page 40 This Page Intentionally Left Blank. Powerware BPIV Parallel Cabinet Installation and Operation 3--8 164201409 REV. B 101503...
  • Page 41: Parallel System Operating Instructions

    Observe all DANGER, CAUTION, and WARNING notices affixed to the inside and outside of the equipment. • Always conform to the more detailed safety precautions described in “Important Safety Instructions” section of Chapter 6. Powerware BPIV Parallel Cabinet Installation and Operation 4--1 164201409 REV. B 101503...
  • Page 42: Symbols, Controls, And Indicators

    Stop and refer to the Operator’s Manual for more information. RISK OF ELECTRIC SHOCK There is a risk of electric shock present, and you should observe associated warnings. The UPS contains high voltages. Powerware BPIV Parallel Cabinet Installation and Operation 4--2 164201409 REV. B 101503...
  • Page 43: Parallel Cabinet Indicator Lights

    ON BYPASS --- Parallel System is on Bypass. NORMAL OPERATION ON BYPASS PARALLEL CABINET Figure 4 ---1. Powerware BPIV 15 kVA and 30 kVA Parallel Cabinet Indicators Powerware BPIV Parallel Cabinet Installation and Operation 4--3 164201409 REV. B 101503...
  • Page 44: Operation

    Operation The following procedures provide instructions for operating the Parallel System. Refer to the Powerware BPIV UPS Installation and Operation manual referenced in the Introduction to this manual, for UPM operating instructions. NOTE: Before starting the Parallel System ensure all installation tasks are complete and a preliminary startup has been performed by authorized service personnel.
  • Page 45: Starting The Parallel System In Bypass Mode

    Observe monitor screens on all UPMs becoming active as an indication of logic power. Press the System Control pushbutton on any UPM. The System Control screen appears on each UPM. Powerware BPIV Parallel Cabinet Installation and Operation 4--5 164201409 REV. B 101503...
  • Page 46: Transfer From Normal Mode To Bypass Mode

    The Parallel System is now operating in the Normal mode and the NORMAL status indicator is illuminated. The UPM PPU status indicates ONLINE and the critical load is protected from commercial power interruptions and abnormalities. Powerware BPIV Parallel Cabinet Installation and Operation 4--6 164201409 REV. B 101503...
  • Page 47: Single Upm Shutdown

    If it is necessary to isolate the UPM from the critical bus, contact Customer Service (refer to Getting Help in the Introduction to this manual). Powerware BPIV Parallel Cabinet Installation and Operation 4--7 164201409 REV. B...
  • Page 48: Restarting A Single Upm

    The rectifier and inverter turn on. When the inverter reaches full voltage, the UPM synchronizes with the output and closes the output contactor. The UPM is online, in parallel with the other system UPMs. Powerware BPIV Parallel Cabinet Installation and Operation 4--8 164201409 REV. B...
  • Page 49: Parallel System And Critical Load Shutdown

    Power is present inside the UPM cabinets due to internal batteries. Open all UPM input and bypass (if dual feed) feeder circuit breakers. Open the Parallel Cabinet bypass input feeder circuit breaker. Load is now de-energized. Powerware BPIV Parallel Cabinet Installation and Operation 4--9 164201409 REV. B 101503...
  • Page 50: Using The Upm Load Off Pushbutton

    Do not attempt to restart the system after Load Off until the cause of the shutdown has been identified and cleared. To restart the UPM after pressing the LOAD OFF pushbutton, follow the procedure in paragraph 4.4.6. Powerware BPIV Parallel Cabinet Installation and Operation 4--10 164201409 REV. B 101503...
  • Page 51: Using The Remote Emergency Power Off Switch

    NOTE: The following instructions are for the Powerware supplied REPO switch. If a customer supplied REPO switch is used it may not activate in the same manner.
  • Page 52 This Page Intentionally Left Blank. Powerware BPIV Parallel Cabinet Installation and Operation 4--12 164201409 REV. B 101503...
  • Page 53: Responding To System Events

    (For descriptions of the Parallel cabinet status indicators refer to Chapter 4 “Parallel System Operating Instructions”, and for descriptions of the UPM status indicators, refer to “Using the Control Panel” in the Powerware BPIV UPS Installation and Operation manual referenced in the Introduction to this manual.)
  • Page 54: System Event Messages

    Check Boost OK HA Condition Cleared Check CSB Setup HA Service Required Check CSB Setup OK HA Condition Cleared Check Inverter HA Service Required Check Inverter OK HA Condition Cleared Powerware BPIV Parallel Cabinet Installation and Operation 5--2 164201409 REV. B 101503...
  • Page 55 Gate Driver Failed 1 HA Service Required Gate Driver Failed 1 OK HA Condition Cleared Heat Sink Thermistor Failure HA Service Required Heat Sink Thermistor Failure OK HA Condition Cleared Powerware BPIV Parallel Cabinet Installation and Operation 5--3 164201409 REV. B 101503...
  • Page 56 HA Condition Cleared Output Phase Rotation HA User Action Required Output Phase Rotation OK HA Condition Cleared Parallel Setup Error Service Required Parallel Setup Error OK Condition Cleared Powerware BPIV Parallel Cabinet Installation and Operation 5--4 164201409 REV. B 101503...
  • Page 57 Warning: Battery Time is Low OK HA Condition Cleared Table Key To Log Column HA --- Event recorded in History and Active Logs. --- Event recorded in Active Log only. Powerware BPIV Parallel Cabinet Installation and Operation 5--5 164201409 REV. B 101503...
  • Page 58 HA Information Only Call Phone # 4 Clear HA Condition Cleared Calling Unsuccessful Information Only Calling Phone #1 HA Information Only Calling Phone #1 OK HA Condition Cleared Powerware BPIV Parallel Cabinet Installation and Operation 5--6 164201409 REV. B 101503...
  • Page 59 Phone #2 Failed Information Only Phone #3 Failed Information Only Phone #4 Failed Information Only SBM IO 1 Not Reporting Information Only SBM IO Not Reporting OK Condition Cleared Powerware BPIV Parallel Cabinet Installation and Operation 5--7 164201409 REV. B 101503...
  • Page 60 UPS MOB Open OK Condition Cleared System Not Redundant Table Key To Log Column HA --- Event recorded in History and Active Logs. --- Event recorded in Active Log only. Powerware BPIV Parallel Cabinet Installation and Operation 5--8 164201409 REV. B 101503...
  • Page 61 UPS Power Supply OK HA Service Status Table Key To Log Column HA --- Event recorded in History and Active Logs. --- Event recorded in Active Log only. Powerware BPIV Parallel Cabinet Installation and Operation 5--9 164201409 REV. B 101503...
  • Page 62 Load Off Normal Mode PPU On PPU Off Table Key To Log Column HA --- Event recorded in History and Active Logs. --- Event recorded in Active Log only. Powerware BPIV Parallel Cabinet Installation and Operation 5--10 164201409 REV. B 101503...
  • Page 63: Maintaining The Parallel System

    Regular routine checks of operation and system parameters will enable your system to function efficiently for many trouble-free years. NOTE: Refer to the Powerware BPIV UPS Installation and Operation Manual, referenced in the Introduction to this manual, for UPM maintenance.
  • Page 64 Suivre les précautions qui s’imposent. • Pour le remplacement, utiliser le même nombre et modéle des batteries. • L’élimination des batteries est règlementée. Consulter les codes locaux à cet effet. Powerware BPIV Parallel Cabinet Installation and Operation 6--2 164201409 REV. B 101503...
  • Page 65: Performing Preventive Maintenance

    Maintenance Training A basic training course, available from Powerware, gives you a competent working knowledge of the Parallel System operation and teaches you how to perform first level corrective maintenance. For more information about training and other services, contact the Powerware Training Coordinator in Raleigh, North Carolina, or call Powerware field service at 1 -- 800 -- 843 -- 9433.
  • Page 66 This Page Intentionally Left Blank. Powerware BPIV Parallel Cabinet Installation and Operation 6--4 164201409 REV. B 101503...
  • Page 67: Product Specifications

    Model 30 kVA (2 Capacity/0 Redundant): 166.6 Amps Model 30 kVA (2 Capacity/1 Redundant): 166.6 Amps Model 30 kVA (3 Capacity/0 Redundant): 249.9 Amps Model 30 kVA (3 Capacity/1 Redundant): 249.9 Amps Powerware BPIV Parallel Cabinet Installation and Operation 7--1 164201409 REV. B 101503...
  • Page 68: Parallel Cabinet Output

    Electrostatic Discharge (ESD) Meets IEC 801---2 specifications. Withstands up Immunity to 25 kV pulse without damage and with no disturbance or adverse effect to the critical load. Powerware BPIV Parallel Cabinet Installation and Operation 7--2 164201409 REV. B 101503...
  • Page 69: Appendix A --- Customer Information

    Parallel Cabinet • 164201409---5 Oneline Drawings of Parallel System • 164201409---6 Location of Parallel Cabinet Terminals Powerware BPIV 15 kVA and 30 kVA • 164201409---7 Parallel Cabinet Controls and Indicators • 164201409---8 Parallel Cabinet Dimensions Powerware BPIV 15 kVA and 30 kVA...
  • Page 70 UPM disconnect switches must be wired in order starting with UPM 1 (e.g., UPM 1 wired to UPM disconnect switch 1). DESCRIPTION: POWER WIRING INSTALLATION NOTES NOTE: Callout letter DRAWING NO: SHEET: map to drawing #164201409---5 164201409---1 1 of 11 REVISION: DATE: 101503 Powerware BPIV Parallel Cabinet Installation and Operation A ---2 164201409 REV. B 101503...
  • Page 71 Minimum conductor size (number per  ) DESCRIPTION: POWER WIRING INSTALLATION NOTES NOTE: Callout letter DRAWING NO: SHEET: map to drawing #164201409---5 164201409---1 2 of 11 REVISION: DATE: 101503 Powerware BPIV Parallel Cabinet Installation and Operation A ---3 164201409 REV. B 101503...
  • Page 72 Minimum conductor size (number per  ) DESCRIPTION: POWER WIRING INSTALLATION NOTES NOTE: Callout letter DRAWING NO: SHEET: map to drawing #164201409---5 164201409---1 3 of 11 REVISION: DATE: 101503 Powerware BPIV Parallel Cabinet Installation and Operation A ---4 164201409 REV. B 101503...
  • Page 73 Minimum conductor size (number per  ) DESCRIPTION: POWER WIRING INSTALLATION NOTES NOTE: Callout letter DRAWING NO: SHEET: map to drawing #164201409---5 164201409---1 4 of 11 REVISION: DATE: 101503 Powerware BPIV Parallel Cabinet Installation and Operation A ---5 164201409 REV. B 101503...
  • Page 74 Minimum conductor size (number per  ) DESCRIPTION: POWER WIRING INSTALLATION NOTES NOTE: Callout letter DRAWING NO: SHEET: map to drawing #164201409---5 164201409---1 5 of 11 REVISION: DATE: 101503 Powerware BPIV Parallel Cabinet Installation and Operation A ---6 164201409 REV. B 101503...
  • Page 75 Minimum conductor size (number per  ) DESCRIPTION: POWER WIRING INSTALLATION NOTES NOTE: Callout letter DRAWING NO: SHEET: map to drawing #164201409---5 164201409---1 6 of 11 REVISION: DATE: 101503 Powerware BPIV Parallel Cabinet Installation and Operation A ---7 164201409 REV. B 101503...
  • Page 76 Table M and N for conduit requirements. Drawing 164201409---6 shows the location of the power cable terminals inside the Parallel Cabinet. Table K. Powerware BPIV Parallel Cabinet Power Cable Terminations 15 kVA 1+1, 2+0, 2+1, 3+0, and 3+1 Configuration...
  • Page 77 AC Input to Bypass (A, B, C, Neut, Gnd) Output (A, B, C, Neut, Gnd) DESCRIPTION: POWER WIRING INSTALLATION NOTES DRAWING NO: SHEET: 164201409---1 8 of 11 REVISION: DATE: 101503 Powerware BPIV Parallel Cabinet Installation and Operation A ---9 164201409 REV. B 101503...
  • Page 78 AC Input to Bypass (A, B, C, Neut, Gnd) Output (A, B, C, Neut, Gnd) DESCRIPTION: POWER WIRING INSTALLATION NOTES DRAWING NO: SHEET: 164201409---1 9 of 11 REVISION: DATE: 101503 Powerware BPIV Parallel Cabinet Installation and Operation A ---10 164201409 REV. B 101503...
  • Page 79 Table O in accordance with the National Electrical Code, ANSI/NFPA 70. DESCRIPTION: POWER WIRING INSTALLATION NOTES DRAWING NO: SHEET: 164201409---1 10 of 11 REVISION: DATE: 061502 Powerware BPIV Parallel Cabinet Installation and Operation A ---11 164201409 REV. B 101503...
  • Page 80 225A BPIV ---30 (2+1) 350A BPIV ---30 (3+0) 350A BPIV ---30 (3+1) DESCRIPTION: POWER WIRING INSTALLATION NOTES DRAWING NO: SHEET: 164201409---1 11 of 11 REVISION: DATE: 061502 Powerware BPIV Parallel Cabinet Installation and Operation A ---12 164201409 REV. B 101503...
  • Page 81: Customer Interface

    Refer to Tables Q and to Chapter 2, paragraph 2.3.3 of this manual for Parallel Cabinet customer interface wiring. Refer to the Powerware BPIV UPS Installation and Operation manual, referenced in the Introduction to this manual, for customer interface terminal locations in the UPMs.
  • Page 82 UPMs and the Parallel Cabinet can be placed in any physical order, but must be DRAWING NO: SHEET: 164201409---2 2 of 2 wired in the order shown in the drawing. REVISION: DATE: 061502 Powerware BPIV Parallel Cabinet Installation and Operation A ---14 164201409 REV. B 101503...
  • Page 83 0---40˚C (32---104˚F) Recommended Operating Range: 20---25˚C (68---77˚F) Maximum Relative Humidity: 95%, non-condensing DESCRIPTION: PHYSICAL FEATURES AND REQUIREMENTS DRAWING NO: SHEET: 164201409---3 1 of 1 REVISION: DATE: 061502 Powerware BPIV Parallel Cabinet Installation and Operation A ---15 164201409 REV. B 101503...
  • Page 84 Powerware BPIV Parallel Cabinet DESCRIPTION: PARALLEL CABINET DRAWING NO: SHEET: 164201409---4 1 of 1 REVISION: DATE: 101503 Powerware BPIV Parallel Cabinet Installation and Operation A ---16 164201409 REV. B 101503...
  • Page 85 ONELINE DRAWINGS OF PARALLEL SYSTEM the same source. DRAWING NO: SHEET: 164201409---5 1 of 3 2. A bypass neutral feeder must be REVISION: DATE: supplied. 061502 Powerware BPIV Parallel Cabinet Installation and Operation A ---17 164201409 REV. B 101503...
  • Page 86 DESCRIPTION: ONELINE DRAWINGS OF PARALLEL SYSTEM the same source. DRAWING NO: SHEET: 2 of 3 164201409---5 2. A bypass neutral feeder must be supplied. REVISION: DATE: 061502 Powerware BPIV Parallel Cabinet Installation and Operation A ---18 164201409 REV. B 101503...
  • Page 87 ONELINE DRAWINGS OF PARALLEL SYSTEM the same source. DRAWING NO: SHEET: 164201409---5 3 of 3 2. A bypass neutral feeder must be REVISION: DATE: 061502 supplied. Powerware BPIV Parallel Cabinet Installation and Operation A ---19 164201409 REV. B 101503...
  • Page 88 PHASE B (E2) FROM PHASE C (E3) UPM 3 NEUTRAL (E12) LEFT VIEW DESCRIPTION: LOCATION OF PARALLEL CABINET TERMINALS POWERWARE BPIV 15 kVA and 30 kVA DRAWING NO: SHEET: 164201409---6 1 of 8 REVISION: DATE: 101503 Powerware BPIV Parallel Cabinet Installation and Operation A ---20 164201409 REV.
  • Page 89 PHASE B (E2) PHASE C (E3) FROM UPM 4 NEUTRAL (E12) RIGHT VIEW DESCRIPTION: LOCATION OF PARALLEL CABINET TERMINALS POWERWARE BPIV 15 kVA and 30 kVA DRAWING NO: SHEET: 164201409---6 2 of 8 REVISION: DATE: 101503 Powerware BPIV Parallel Cabinet Installation and Operation A ---21 164201409 REV.
  • Page 90 (A, B, C, N) (SEE SHEET 5 AC OUTPUT TO FOR DETAILS) CRITICAL LOAD (A, B, C, N) DESCRIPTION: LOCATION OF PARALLEL CABINET TERMINALS POWERWARE BPIV 15 kVA and 30 kVA DRAWING NO: SHEET: 164201409---6 3 of 8 REVISION: DATE: 101503...
  • Page 91 (A, B, C, N) (SEE SHEET 6 AC OUTPUT TO FOR DETAILS) CRITICAL LOAD (A, B, C, N) DESCRIPTION: LOCATION OF PARALLEL CABINET TERMINALS POWERWARE BPIV 15 kVA and 50 kVA DRAWING NO: SHEET: 164201409---6 4 of 8 REVISION: DATE: 101503...
  • Page 92 15 kVA 1+1, 2+0, 2+1, 3+0, and 3+1 Configuration 30 kVA 1+1, 2+0, and 2+1 Configurations INPUT/OUTPUT TERMINAL BLOCK NEUTRAL (3E12) DESCRIPTION: LOCATION OF PARALLEL CABINET TERMINALS POWERWARE BPIV 15 kVA and 30 kVA DRAWING NO: SHEET: 164201409---6 5 of 8 REVISION: DATE:...
  • Page 93 PARALLEL CABINET POWER TERMINALS 30 kVA 3+0, and 3+1 Configurations INPUT/OUTPUT TERMINAL BLOCK NEUTRAL (3E12) DESCRIPTION: LOCATION OF PARALLEL CABINET TERMINALS POWERWARE BPIV 15 kVA and 30 kVA DRAWING NO: SHEET: 164201409---6 6 of 8 REVISION: DATE: 101503 Powerware BPIV Parallel Cabinet Installation and Operation A ---25 164201409 REV.
  • Page 94 REAR ENTRY CONDUIT LANDING FOR BYPASS INPUT AND LOAD OUTPUT CONNECTIONS (REMOVE PANEL TO DRILL OR PUNCH CONDUIT HOLES.) DESCRIPTION: LOCATION OF PARALLEL CABINET TERMINALS POWERWARE BPIV 15 kVA and 30 kVA DRAWING NO: SHEET: 164201409---6 7 of 8 REVISION: DATE:...
  • Page 95 FRAME GROUND INTERFACE WIRING WIREWAY CUSTOMER INTERFACE TERMINALS (TB2) TOP VIEW DESCRIPTION: LOCATION OF PARALLEL CABINET TERMINALS POWERWARE BPIV 15 kVA and 30 kVA DRAWING NO: SHEET: 164201409---6 8 of 8 REVISION: DATE: 101503 Powerware BPIV Parallel Cabinet Installation and Operation A ---27 164201409 REV.
  • Page 96 An illuminated LED represents a condition where a service disconnect switch is open and should not be closed. These switches are not customer accessible and a qualified service representative must be contacted to perform corrective action. To schedule a service call, contact Powerware Customer Service. DESCRIPTION: PARALLEL CABINET...
  • Page 97 An illuminated LED represents a condition where a service disconnect switch is open and should not be closed. These switches are not customer accessible and a qualified service representative must be contacted to perform corrective action. To schedule a service call, contact Powerware Customer Service. DESCRIPTION: PARALLEL CABINET...
  • Page 98 PARALLEL CABINET DESCRIPTION: PARALLEL CABINET DIMENSIONS POWERWARE BPIV 15 kVA and 30 kVA DRAWING NO: SHEET: 164201409---8 Dimensions are in millimeters and [inches] 1 of 2 REVISION: DATE: 101503 Powerware BPIV Parallel Cabinet Installation and Operation A ---30 164201409 REV. B...
  • Page 99 PARALLEL CABINET Dimensions are in millimeters and [inches] DESCRIPTION: PARALLEL CABINET DIMENSIONS POWERWARE BPIV DRAWING NO: SHEET: 164201409---8 2 of 2 REVISION: DATE: 101503 Powerware BPIV Parallel Cabinet Installation and Operation A ---31 164201409 REV. B 101503...
  • Page 100 This Page Intentionally Left Blank. Powerware BPIV Parallel Cabinet Installation and Operation A ---32 164201409 REV. B 101503...
  • Page 101: Warranty

    All parts requiring replacement for the Factory Warranty period. If, in the opinion of Powerware, the Unit fails to meet published specifications and the defect is within the terms of this warranty, the Unit will be repaired or replaced at the option of Powerware with no charge for replacement parts. Labor required, to make...
  • Page 102 This Page Intentionally Left Blank. Powerware BPIV Parallel Cabinet Installation and Operation W--2 164201409 REV. B 101503...
  • Page 104 *164201409B* 164201409 Rev B...

This manual is also suitable for:

Bpiv 15 kva

Table of Contents