Warranty - Powerware BPIV Installation & Operation Manual

10–15 kva/20–30 kva
Table of Contents

Advertisement

Table A. INPUT/OUTPUT Ratings & External Wiring Requirements for
Basic unit ratings at
0.9 lagging PF load
gg g
AC Input to UPS Rectifier
AC Input to UPS Rectifier
AC
AC
3 , 1 gnd
3 , 1 gnd
INPUT
Minimum conductor size (number per  )
*(Maximum amps includes full load current plus
battery recharge current)
AC Input to Module Bypass (UPS Bypass)
Full Load Current
Full Load Current
AC
AC
INPUT
Minimum conductor size (number per  )
DC Input from External Battery Source to UPS
DC
( ) p
(1) positive, (1) negative, (1) gnd
INPUT
INPUT
Minimum conductor size (number per pole)
AC Output to Critical Load
AC
AC
Full Load Current 3 , (1) Neutral, (1) gnd
Full Load Current 3  (1) Neutral (1) gnd
OUTPUT
Minimum conductor size (number per  )
Read and understand the following notes while planning your installation:
1.
Refer to national and local electrical codes for acceptable external wiring practices.
2.
The bypass feed into this equipment utilizes four wires. The rectifier feed into this equipment
utilizes three wires. However, the phases must be symmetrical about ground (i.e., from a Wye
source) for proper equipment operation. Failure to follow these instructions will void the
product warranty.
3.
Material and labor for external wiring requirements are to be provided by designated personnel.
4.
For external wiring, use 90° C copper wire. See the appropriate column in Tables A through K.
5.
Wire ampacities are chosen from Table 310---16 of the NEC.
6.
A bypass neutral feeder must be supplied.
7.
Refer to Section I of this manual for installation Instructions.
8.
UPS systems not using an external battery source are supplied with internal batteries prewired
to the UPS at the factory. External Line-up and Match Battery cabinets are provided with with
quick disconnect cables for connection to the UPS. No external wiring is required for Line-up
and Match battery cabinets. All products can be connected to an external battery source
through the DC connections terminal block. An external DC ground is established through the
grounding terminal in the bottom of the cabinet.
NOTE:
Callout letter
map to drawing #164201406---6
A ---2
Powerware BPIV---15/10
(Without Options Cabinet)
Ratings
(0.95min.PF)
(0.95min.PF)
3 , (1) Neutral, (1) gnd
3 , (1) Neutral, (1) gnd
, ( )
g
, ( ) g
and
,
,
,
Units
KVA
KW
INPUT/OUTPUT
VOLTAGE
A
AWG or kcmil(ea)
Amps
B
AWG or kcmil(ea)
VDC (Nominal)
C
Amps
(See note 8)
AWG or kcmil(ea)
Amps
D
AWG or kcmil(ea)
DESCRIPTION:
POWER WIRING INSTALLATION NOTES
DRAWING NO:
164201406---1
REVISION:
C
Powerware BPIV (10 kVA- -30 kVA) Installation and Operation
Rating 50/60 Hz
10
208
Amps*
Amps*
36
36
8 (1)
27.8
8 (1)
288
34
8 (1)
27.8
8 (1)
SHEET:
DATE:
013004
164201406 Rev. C 013004
9
1 of 14