Powerware BPIV Installation & Operation Manual page 181

10–15 kva/20–30 kva
Table of Contents

Advertisement

Basic unit ratings at
0.9 lagging PF load
AC Input to UPS Rectifier
AC
AC
Transformer
INPUT (0.95min.PF)
INPUT
(0 95min PF)
3 , 1 gnd
3 , 1 gnd
AC Input to UPS Bypass
AC
AC
Transformer
INPUT
INPUT Full Load Current
Full Load Current
3 , 1 Neutral, 1 gnd
3 , 1 Neutral, 1 gnd
NOTE:
Callout letter
map to drawing #164201406---6
Powerware BPIV (10 kVA- -30 kVA) Installation and Operation
164201406 Rev. C 013004
Table I. Ratings & External Wiring Requirements for
Powerware BPIV (20 kVA---30 kVA)
Options Cabinet INPUT and BYPASS Transformers
g
Series/
Model
30/20
30/20
30/20
p
30/25
30/25
30/25
A
30/30
30/30
30/30
30/20
30/20
30/20
p
yp
30/25
30/25
30/25
30/30
B
30/30
30/30
and
,
,
,
Ratings 50/60 Hz
Voltage
Input
Output
kVA/KW
20/18.0
208
20/18.0
480
20/18.0
600
25/22.5
208
25/22.5
480
25/22.5
600
30/27.0
208
30/27.0
480
30/27.0
600
20/18.0
208
20/18.0
480
20/18.0
600
25/22.5
208
25/22.5
480
25/22.5
600
30/27.0
208
30/27.0
480
30/27.0
600
DESCRIPTION:
POWER WIRING INSTALLATION NOTES
DRAWING NO:
164201406---1
REVISION: C
Conductor
Input
Input
Minimum
Current
Size
(Amps)
208
70.0
3
208
30.3
8
208
24.0
10
208
90.0
2
208
39.0
8
208
31.2
8
208
100
1
208
43.3
6
208
34.7
8
208
69.4
4
208
30
10
208
24
12
208
83
4
208
36
8
208
28.8
10
208
97
2
208
42
8
208
33.6
8
SHEET:
DATE:
013004
6 of 14
A ---7

Advertisement

Table of Contents
loading

Table of Contents