15.4 Environmental Specifications

Operating Temperature
Operating Altitude
Storage Temperature
Relative Humidity (operating and
storage)
Acoustical Noise
EMI Suppression
Electrostatic Discharge (ESD)
Immunity
System Efficiency at Full Unity
Power Factor Load and Nominal
Input Voltage
Powerware 9330 (10 kVA- -40 kVA) Installation and Operation
164201300 REV. G 061502
0 to 40˚C without derating. The recommended
operating temperature is 25˚C.
Maximum 1500m (5000 ft) at 40_C without
derating
---20 to +70˚C (prolonged storage above 40˚C
will cause rapid battery self-discharge)
95% maximum, noncondensing
60 dBA at a 1m distance
Meets FCC Regulation 47, Part 15, for class A
devices
Meets IEC 801---2 specifications. Withstands up
to 25 kV pulse without damage and with no
disturbance or adverse effect to the critical load.
208V Models:
92% in Normal Mode
98% in High Efficiency Mode
480V Models:
90% in Normal Mode
96% in High Efficiency Mode
600V Models:
90% in Normal Mode
96% in High Efficiency Mode