Powerware BPIV Installation & Operation Manual page 196

10–15 kva/20–30 kva
Table of Contents

Advertisement

6.
The basic environmental requirements for operation of the UPS system are:
Ambient Temperature Range:
Recommended Operating Range: 20---25˚C (68---77˚F)
Maximum Relative Humidity:
The UPS ventilation requirements are shown in Table Z.
Table Z. Air Conditioning or Ventilation Requirements
Ratings
10 KVA
15 KVA
20 KVA
25 KVA
30 KVA
A ---22
During Full Load Operation
Powerware BPIV (10 kVA-- 30 kVA)
Input/Output Voltage
208/208
480/208
480/480, 600/208
208/208
480/208
480/480, 600/208
208/208
480/208, 600/208
480/480
208/208
480/208, 600/208
480/480
208/208
480/208, 600/208
480/480
0---40˚C (32---104˚F)
95%, noncondensing
Heat Rejection
BTU/hr ¢ 1000/hr (Kg---cal/hr)
2.7 (0.7)
3.4 (0.9)
3.9 (1.0)
4.0 (1.0)
5.1 (1.2)
5.8 (1.4)
5.3 (1.3)
6.7 (1.6)
7.7 (1.9)
6.7 (1.7)
8.5 (2.1)
9.7 (2.4)
8.1 (2.1)
10.2 (2.6)
11.7 (3.0)
DESCRIPTION:
PHYSICAL FEATURES AND REQUIREMENTS
DRAWING NO:
164201406---3
REVISION:
C
Powerware BPIV (10 kVA- -30 kVA) Installation and Operation
SHEET:
2 of 2
DATE:
013004
164201406 Rev. C 013004