Powerware BPIV Installation & Operation Manual page 70

10–15 kva/20–30 kva
Table of Contents

Advertisement

Figure 4 ---2. Remote EPO Control (inside view of cover and enclosure bottom)
3.
Mount cover to Remote EPO switch enclosure bottom, as shown in
Figure 4---2, for easier wiring.
NOTE: A separate conduit is required for each UPS connected to the Remote EPO
switch.
4.
Install wiring from the Remote EPO switch using ½-in. conduit through the
Customer Interface conduit landing plate on the rear of the UPS cabinet. Refer
to Appendix A, Drawing 164201406---8, for conduit landing area and terminal
board location, and Drawing 164201406---2 for terminal wiring assignments.
5.
Connect the Remote EPO wiring as shown in Tables 4---1 and 4---2 and Figure
4---2.
6.
If you are installing multiple Remote EPO stations, wire additional stations in
series with the first Remote EPO.
4--2
TB2
COVER
TB1
ENCLOSURE BOTTOM
Powerware BPIV (10 kVA- -30 kVA) Installation and Operation
164201406 Rev. C 013004