Product Specifications - Powerware 9390 Installation & Operation Manual

40-80 kva
Hide thumbs Also See for 9390:
Table of Contents

Advertisement

Chapter 14
14.1 Model Numbers
The UPS systems are housed in free-standing, cabinets with safety shields behind the doors.
The UPS systems are available in 50/60 Hz with various output power ratings.
The following sections detail the input, output, environmental, and battery specifications
for the UPS.
14.2 UPS System Input
Powerware
9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev A
®

Product Specifications

System
Powerware 9390-40
Powerware 9390-80
Operating Input Voltage
(Nominal +10/–15%)
Operating Input
Frequency Range
Operating Input Current
Input Current Harmonic
Content
Power Factor
Line Surges
Battery Voltage
Models
40 kVA
80 kVA
208 Vac for operation from 177 Vac to 229 Vac
480 Vac for operation from 408 Vac to 528 Vac
5 Hz
¦
See Appendix A, Table E or Table F.
Reduced for Generator
Adjustable
5% THD at full load
Minimum 0.99
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801-4
384 Vdc (208V units only)
432 Vdc
480 Vdc
Frequency
50/60 Hz
50/60 Hz
14-1