Chapter 8
WARNING
Before sliding out the HP NetServer LC 2000r, ensure the
anti-tip foot is still extended from the front of the rack. A
tip-over hazard exists, so never slide more than one
component out of the rack at a time.
1. Ensure the HP NetServer LC 2000r is pushed all the way into the rack.
2. At the rear of the HP NetServer, place rack nuts on the left column in the
12th and 14th holes above the baseline (bottom) of the NetServer.
See Figure 8-11.
Left
Rear of
Rack
Attach nuts to this face
of the left rear column.
Figure 8-11. Attaching the Rack Nuts to the Left Column
3. Orient the Cable Management Arm as shown in Figure 8-11.
4. Match the inner flange mounting holes with the two captive nuts at the rear
of the NetServer. See Figure 8-12.
The captive nuts are located near the external SCSI Connector (knockout)
location.
92
Rack-Mounting the HP NetServer
"
"
represents
#
the EIA unit
numbers on the
#
rack columns.
#
#
#
#
Bottom of
HP NetServer
14th Hole
from Bottom
12th Hole
from Bottom
9th Hole
from Bottom
7th Hole
from Bottom