3.5 CONFIG MODE, CONTINUED
4. Left click on Settings or press Alt+S on the PC keyboard. Left click on Port or
press P on the PC keyboard.
5. Left click on TARGET to define the communication settings for the PC serial port
connected to the ULTRAKey.
a. Set the Port: field to the port on the PC connected to the ULTRAKey. Click on
b. Set the Baud: field to 38400 (recommended). This can be set to any of the
c. Set the Parity, Data Bits, and Stop Bits. Again, these settings must match the
d. Left click on OK to save settings.
518750-2960
Rev. F
the down arrow beside the Port: field to display the available settings.
available settings as long as COM3 on the ULTRAKey is set at the same rate.
settings of COM3 on the ULTRAKey. The data bits and stop bits must be set at
8 and 1, respectively.
41
HEMU001007
10/15/04