- HP Openview
To provide SNMP alarm notification, on the server Web Interface use the Configure Trap
Destinations screen to set up SNMP destinations in the corporate NMS.
Administering INADS phone numbers and Enabling alarms to INADS
The following procedure, using the primary server's Linux shell commands, administers the
dial-out modem to send alarms in the OSS method. In this example, the primary server is an
S8300, and the services support agency is Avaya's Initialization and Administration System
(INADS).
Perform this task after all Communication Manager administration is complete.
Note:
Do these steps only if the S8300 is the primary controller and the customer has a
Note:
maintenance contract with Avaya. Use the information you acquired from the
ART tool (see
address, if
Also, a USB modem must have already been installed.
To add INADS phone numbers and Enable alarms to INADS
1. With a direct connection to the S8300 Services port, open a telnet session and log in as
craft (or dadmin).
2. At the Linux prompt, type almcall -f INADS phone number -s <second-number>
and press Enter.
3. At the prompt, type almenable -d b -s y and press Enter.
4. Type almenable and press Enter to verify that the alarms are enabled.
5. Log off
Configuring the G700 Media Gateway to send its traps
to a network management system (NMS)
Configuring the G700 Media Gateway to send SNMP traps to the primary server can be
accomplished by two commands:
P330 stack processor CLI command set snmp community trap [community
string]
Media Gateway Processor (MGP) CLI command set snmp trap <IP address>
enable
Running the Automatic Registration Tool (ART) for the INADS IP
necessary).
Set Up SNMP Alarming on the G700
Issue 7 January 2005
189