UPS Maintenance
84
Powerware
To switch the UPS to maintenance bypass from Normal mode
(wall-mounted operation):
1. Press the red button beside the Maintenance Bypass switch.
2. Turn the switch handle through the LINE position to the
SERVICE position.
The battery circuit breaker trips, and the UPS is now bypassed,
with the load powered by utility power.
3. The UPS automatically shuts down.
To return to Normal mode from maintenance bypass (wall-mounted
operation):
1. If an optional isolation transformer is installed, switch the input
circuit breaker to the ON position.
2. Turn the Maintenance Bypass switch to the LINE position.
The UPS starts up in Bypass mode, with the load still powered
by utility power.
3. Switch the UPS battery circuit breaker to the ON position.
NOTE
Wait until the
Step 4; otherwise, power to the load may be lost.
4. Turn the Maintenance Bypass switch to the UPS position to
return to Normal mode. The UPS is now powering the load.
9155 UPS (8–15 kVA) User's Guide
®
indicator illuminates before proceeding to
164201553 Rev D www.powerware.com