Table 9. UPS Terminal Block Wiring
Wire Function
Input
p
Ground
L1
Neutral
L2
Output
p
L1
Neutral
L2
Ground
*Use only 90°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC
Code Table 310-16.
Powerware
9155 UPS (8–15 kVA) User's Guide
®
9. Connect the wiring from the bypass switch to the UPS terminal
block.
See Table 9 for specifications and Figure 26 for a detailed view
of the UPS terminal block.
Terminal
Minimum
Position
Wire Size*
TB1-1
8 AWG
TB1-3
3 AWG
TB1-4
3 AWG
TB1-5
3 AWG
TB1-6
3 AWG
TB1-7
3 AWG
TB1-8
3 AWG
TB1-9
8 AWG
TB1
164201553 Rev D www.powerware.com
S
Wall-Mounted Bypass Switch Installation
Tightening
Torque
25 lb in
25 lb in
(2.83 Nm)
25 lb in
25 lb in
(2.83 Nm)
1
3
4
5
6
2
Input
Figure 26. UPS Terminal Block
Conduit Connection
(Entry Size)
2 access hole for
2" access hole for
1-1/2" conduit
2 access hole for
2" access hole for
1-1/2" conduit
7
8
9
Output
45