Powerware 9155 User Manual page 24

8-15 kva
Hide thumbs Also See for 9155:
Table of Contents

Advertisement

UPS Only Installation
Table 2. UPS Terminal Block Wiring
Wire Function
Input
p
Ground
L1
Neutral
L2
Output
p
L1
Neutral
L2
Ground
*Use only 90°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC
Code Table 310-16.
18
Powerware
NOTE
Input neutral must be wired for proper operation.
Terminal
Minimum
Position
Wire Size*
TB1-1
8 AWG
TB1-3
3 AWG
TB1-4
3 AWG
TB1-5
3 AWG
TB1-6
3 AWG
TB1-7
3 AWG
TB1-8
3 AWG
TB1-9
8 AWG
TB1
8. Replace the UPS wiring access cover.
9. Continue to "Stabilizing the Cabinet" on page 49 to complete
the UPS installation.
9155 UPS (8–15 kVA) User's Guide
®
Tightening
Torque
25 lb in
25 lb in
(2.83 Nm)
25 lb in
25 lb in
(2.83 Nm)
1
3
4
5
6
2
Input
Figure 6. UPS Terminal Block
164201553 Rev D www.powerware.com
S
Conduit Connection
(Entry Size)
2 access hole for
2" access hole for
1-1/2" conduit
2 access hole for
2" access hole for
1-1/2" conduit
7
8
9
Output

Advertisement

Table of Contents
loading