Wall-Mounted Bypass Switch Installation
44
Powerware
7. Install the conduit to the bypass switch cabinet. AC input and
AC output conductors must be run through separate conduit.
UPS output circuits must be installed in a dedicated conduit
system and not shared with other electrical circuits.
8. Hardwire the terminal strip inside the bypass switch cabinet. Use
copper wire that is the appropriate size for the current draw.
See Figure 25 for a detailed view of the terminal strip label.
Figure 25. Wall-Mounted Bypass Switch Terminal Strip Wiring
9155 UPS (8–15 kVA) User's Guide
®
164201553 Rev D www.powerware.com