Wall-Mounted Bypass Switch Installation
42
Powerware
Only qualified service personnel (such as a licensed electrician) should perform
the hardwired installation. Risk of electrical shock.
Use the following procedure to hardwire the wall-mounted bypass
switch:
1. Verify that the electrical connections to the installation site have
been properly installed.
2. A wall-mounted, user-supplied, readily-accessible disconnection
device must be incorporated in the input wiring.
Compare the circuit breaker ratings and wire sizes to the ones in
the following wiring table:
Table 8. Circuit Breaker Ratings
UPS Capacity
Input Circuit Breaker Rating
8 kVA
10 kVA
12 kVA
15 kVA
*Use only 90°C-rated copper wire. Minimum wire size is based on 120/208 full load
ratings applied to NEC Code Table 310-16. Code may require a larger AWG size than
shown in this table because of temperature, number of conductors in the conduit,
or long service runs. Follow local requirements.
NOTE
To accommodate the feature of easy system expandability, it is
recommended that initial installation of the Powerware 9155 UPS contain
wiring to support the maximum capacity of the UPS cabinet.
3. Switch off utility power to the distribution point where the UPS
will be connected. Be absolutely sure there is no power.
4. Determine your equipment's grounding requirements according
to your local electrical code.
9155 UPS (8–15 kVA) User's Guide
®
W A R N I N G
60A
80A
100A
100A
164201553 Rev D www.powerware.com
S
Minimum Wire Size*
2
4 AWG (21.2 mm
)
2
3 AWG (26.7 mm
)
2
2 AWG (33.6 mm
)
2
2 AWG (33.6 mm
)