9155 UPS (8–15 kVA) User's Guide
®
Output overcurrent protection and disconnect switch must be provided
by others.
Figure 20 and Figure 21 beginning on page 37 show the oneline diagrams
of the MBM and PDM with the UPS.
Only qualified service personnel (such as a licensed electrician) should perform
the UPS installation and initial startup. Risk of electrical shock.
Use the following procedure to hardwire the MBM/PDM:
1. Verify that the electrical connections to the installation site have
been properly installed.
2. A wall-mounted, user-supplied, readily-accessible disconnection
device must be incorporated in the input wiring.
Compare the circuit breaker ratings and wire sizes to the ones in
the following wiring table:
Table 6. Circuit Breaker Ratings
UPS Capacity
Input Circuit Breaker Rating
8 kVA
10 kVA
12 kVA
15 kVA
*Use only 90°C-rated copper wire. Minimum wire size is based on 120/208 full load
ratings applied to NEC Code Table 310-16. Code may require a larger AWG size than
shown in this table because of temperature, number of conductors in the conduit,
or long service runs. Follow local requirements.
NOTE
To accommodate the feature of easy system expandability, it is
recommended that initial installation of the Powerware 9155 UPS contain
wiring to support the maximum capacity of the UPS cabinet.
3. Switch off utility power to the distribution point where the UPS
will be connected. Be absolutely sure there is no power.
164201553 Rev D www.powerware.com
S
UPS-Mounted Bypass Switch Installation
W A R N I N G
60A
80A
100A
100A
Minimum Wire Size*
2
4 AWG (21.2 mm
)
2
3 AWG (26.7 mm
)
2
2 AWG (33.6 mm
)
2
2 AWG (33.6 mm
)
33