X-Slot Cards - Powerware 9155 User Manual

8-15 kva
Hide thumbs Also See for 9155:
Table of Contents

Advertisement

Communication
58
Powerware
The cable pins are identified in Figure 37 and the pin functions are
described in Table 10. See Figure 32 on page 53 for serial port location.
Table 10. Communication Port Pin Assignment
Pin
Signal Name
Number
2
TxD
3
RxD
5
GND

X-Slot Cards

X-Slot cards allow the UPS to communicate in a variety of networking
environments and with different types of devices. The Powerware 9155
has two available communication bays for any X-Slot card, including:
ConnectUPS -X Web/SNMP Card - has SNMP and HTTP capabilities as
t
well as monitoring through a Web browser interface; connects to a
twisted-pair Ethernet (10/100BaseT) network. It has a built-in switching
hub that allows three additional network devices to be connected to
the network without the requirement of additional network drops. In
addition, a Powerware Environmental Monitoring Probe can be
attached to obtain humidity, temperature, smoke alarm, and security
information.
Relay Interface Card - has isolated dry contact (Form-C) relay outputs
for UPS status: Utility failure, Low battery, UPS alarm/OK, or On
bypass.
Modbus
Card - allows you to continuously and reliably monitor the
®
UPSs in your Building Management System (BMS).
9155 UPS (8–15 kVA) User's Guide
®
5
9
4
8
3
7
2
6
1
Figure 37. Communication Port
Function
Transmit to external device
Receive from external device
Signal common (tied to chassis)
164201553 Rev D www.powerware.com
S
Direction
from the UPS
Out
In