Powerware 9170 User Manual

Powerware 9170 User Manual

3–18 kva, 50 and 60 hz
Hide thumbs Also See for 9170:
Table of Contents

Advertisement

Quick Links

9170
+
UPS
USER'S GUIDE
3–18 kVA,
50 and 60 Hz
www.powerware.com

Advertisement

Table of Contents
loading

Summary of Contents for Powerware 9170

  • Page 1 9170 USER’S GUIDE 3–18 kVA, 50 and 60 Hz www.powerware.com...
  • Page 2 Powerware is a registered trademark and ConnectUPS and BestDock are trademarks of Powerware Corporation. ECopyright 2000–2003 Powerware, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Powerware.
  • Page 3 Class A EMC Statements FCC Part 15 NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
  • Page 5: Table Of Contents

    ........... . Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 6 ..........Reading the Powerware 9170+ System Logs .
  • Page 7 ............Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 8 Table of Contents Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 9: Introduction

    Chapter 1 Introduction The Powerware 9170 uninterruptible power system (UPS) is a modular UPS that contains battery modules and power control modules (referred to as power modules). These modules plug into a rack cabinet structure containing additional control, communication, and display functions that enable integrated control of all power modules.
  • Page 10: Safety Warnings

    (model ASY-0674) have black labels on the front and produce a single output voltage: 200, 208, 220, 230, or 240 Vac. DO NOT mix the two types of power modules in the same Powerware 9170 cabinet. Do NOT install more than seven power and/or optional battery charger modules in the system.
  • Page 11: Physical Features

    Introduction Physical Features The Powerware 9170 UPS is available in four cabinet sizes. Figure 1 through Figure 6 show the 3-slot and 9-slot configurations and identify basic Powerware 9170 system features. Six-slot and 12-slot cabinets are also available; external battery cabinets are available in 6-, 9-, and 12-slot sizes.
  • Page 12 Introduction Front Panel Display Front Cover Panels Cabinet Base Figure 3. Nine-Slot Cabinet (Front View) Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 13 Cable (optional) Figure 4. Nine-Slot Cabinet (Rear View) Handle/Latch Release Handle Thumbscrew Insertion/Extraction Cams Figure 5. Power Module (ASY-0673 and ASY-0674) Secondary Stop Release Latch Release Figure 6. Battery Module (ASY-0529) Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 14 Introduction Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 15: Installation Setup

    Chapter 2 Installation Setup This chapter explains how to setup and install the Powerware 9170 cabinets: Setup, including clearances and location requirements Caster cart installation Stabilizer bracket installation (for 12-slot cabinets with non-isolated output) Rack-mount installation (for three- and six-slot cabinets)
  • Page 16: Location Requirements

    25 ft (7.6m), transient noise can reappear in the electrical distribution system. If a separate external battery cabinet is installed, the battery cabinets must be adjacent to the Powerware 9170 UPS. If the batteries will be further from the unit than the standard cables allow, contact your service representative or your local distributor for assistance.
  • Page 17: Nine- And Twelve-Slot Cabinets

    19 or “UPS Electrical Installation” on page 37. Nine- and Twelve-Slot Cabinets NOTE The 12-slot Powerware 9170 UPS cabinet with non-isolated output is shipped with two stabilizer brackets. These brackets must be attached to the wall or the floor behind the UPS cabinet (see page 11).
  • Page 18: Caster Cart Installation

    If leveling of the UPS is required, use the foot pads to raise a side or corner before locking them with their lock nuts. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 19: Stabilizer Bracket Installation (Twelve-Slot Cabinet Only)

    Installation Setup Stabilizer Bracket Installation (Twelve-Slot Cabinet Only) The 12-slot Powerware 9170 UPS cabinet with non-isolated output is shipped with two stabilizer brackets. These brackets must be attached to the wall or the floor behind the UPS cabinet. Under all module-loading conditions, they act as a protective stop to prevent the cabinet from falling forward if it is unintentionally pushed away from the wall.
  • Page 20: Rack-Mount Installation (Three- And Six-Slot Cabinet)

    Set the cover aside. Remove the two cabinet side panels (4 panels in 6-slot cabinets) by lifting the top edge. No other hardware must be detached. Store or discard the side panels. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 21 Pivot the ear forward until it is flush against the UPS cabinet side frame. Using three 1/4-20×1/2I Phillips-head bolts, screw the bolts into the metal clip-nuts installed in Step 4. Rack-Mount Ear Figure 10. Rack-Mount Ear Installed Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 22: Floor Anchor Kit Installation

    Floor Anchor Kit Installation An optional floor anchor kit (ASY-0548) is available for all sizes of the Powerware 9170 UPS. The kit helps to stabilize the UPS or battery cabinet in the event of accidental bumps or small floor movements. Any testing to specific seismic requirements is the responsibility of the customer.
  • Page 23 14.5I (36.8 cm) B (3- and 6-slot cabinets) 30.25I (76.8 cm) B (9- and 12-slot cabinets) 34.25I (87 cm) Floor Anchor Bracket Figure 12. Floor Anchor Brackets Bolted to UPS Cabinet Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 24: Moving The Cabinets

    C A U T I O N Do NOT attempt to raise the cabinet with the power or battery modules installed. The Powerware 9170 UPS and the battery cabinet are very heavy with power and battery modules installed. Before moving the cabinets, remove the power and battery modules.
  • Page 25 Do not use the caster bolts to level the cabinet. After properly positioning and leveling the cabinet, insert power and battery modules into the cabinet as described in “UPS Startup” on page 63. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 26 Installation Setup Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 27: Ups With Bypass Electrical Installation

    For hardwired installations, it is recommended that you install a Powerware bypass switch to enable power transfer during maintenance or UPS downtime. If a bypass switch is used, both UPS input and UPS output must be hardwired–...
  • Page 28 UPS with Bypass Electrical Installation External Bypass Switch Service Line Building Load Service Distribution Panel Panel Service Line Service Line User-supplied (If Required) External Batteries (Optional) Figure 13. Typical Installation with a Bypass Switch Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 29: Input Current Ratings

    NOTE To accommodate the feature of easy system expandability, it is recommended that initial installation of the Powerware 9170 contain wiring to support the maximum capacity of the UPS cabinet: 3 kVA for 3-slot cabinets; 9 kVA for 6-slot cabinets; 18 kVA for 9- and 12-slot cabinets.
  • Page 30: Bypass Switches

    If you turn a BBM switch from UPS to LINE, the switch disconnects the load from UPS output power before connecting the load to AC input power. The bypass switch has four positions as described in Table 3. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 31 SERVICE position. For MBB switches, you must press the red button beside the switch before you can change the switch position. Table 4 shows the bypass switch models available for the Powerware 9170 UPS. Table 4. Bypass Switch Specifications...
  • Page 32 UPS with Bypass Electrical Installation Figure 14. Bypass Switch Mounting Dimensions Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 33: Ups Installation With An External Bypass Switch

    Mount the bypass switch within sight of the UPS. If you do not have a Powerware bypass switch or the fuse box or panel is out of sight, you must install a separate disconnect switch next to the UPS.
  • Page 34 Installing this wiring is described in Steps 12 and 13 on page 31. Remove the knockouts in the entrance panel for AC input and AC output wiring. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 35 Table 2 on page 22. Use copper wire that is the appropriate size for the current draw. Figure 16 shows a sample label. Figure 16. Bypass Switch Wiring Label Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 36 200, 208, 220, 230, or 240 Vac, as selected through the front panel display. These modules produce a single output voltage, typically required in Europe, the Middle East, Asia, and Africa. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 37 Figure 19 and Figure 20 describe output wiring configurations for various output voltages. You must also set the operating menu parameter 4-2-4 for the required output voltage as shown in the wiring configuration drawings. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 38 UPS with Bypass Electrical Installation NOTE For Powerware 9170 UPS models with low-voltage hardwire output, it is recommended to divide the total load as equally as possible between X1 and X2, as shown in Figure 19. NOTE Failure to balance the loads may cause an overload alarm even if the full capacity of the UPS has not been reached.
  • Page 39 Remove the jumper between terminals 5 and 6 only if you are wiring from an EPO switch. (See “Changing Parameter Settings” on page 81 for information about accessing menu 4, submenu 3, item 2 to view or change the EPO switch type.) Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 40: System Wiring Diagrams

    L1 – L2 page 29 page 30 page 34 Figure 18b on Figure 20 on Figure 24 on L1 – N page 29 page 30 page 35 *Split-phase power modules required. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 41 External UPS battery cabinets are optional. See “Battery Cabinet Installation” on page 57 for installation instructions. NOTE 7 UPS output circuits shall be installed in dedicated conduit systems and not shared with other electrical circuits. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 42 S 208 Input, 208 Output S 220 Input, 220 Output NOTE 6 S 230 Input, 230 Output S 240 Input, 240 Output Figure 23. External Bypass Switch (L1, L2), Non-Isolated Output, Universal Power Modules Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 43 NOTE 7 S 220 Input, 220 Output NOTE 6 S 230 Input, 230 Output S 240 Input, 240 Output Figure 24. External Bypass Switch (L1, N), Non-Isolated Output, Universal Power Modules Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 44 UPS with Bypass Electrical Installation Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 45: Ups Electrical Installation

    UPS. Without a bypass switch, power to the load cannot be maintained if the UPS is taken completely offline. Building Load Service Distribution Panel Panel User-supplied (If Required) External Batteries (Optional) Figure 25. Typical Installation without a Bypass Switch Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 46: Input Current Ratings

    NOTE To accommodate the feature of easy system expandability, it is recommended that initial installation of the Powerware 9170 contain wiring to support the maximum capacity of the UPS cabinet: 3 kVA for 3-slot cabinets; 9 kVA for 6-slot cabinets; 18 kVA for 9- and 12-slot cabinets.
  • Page 47 (ampacity) wire. Code may require a larger AWG size than shown in this table because of temperature, number of conductors in the conduit, or long service runs. Follow local code requirements. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 48: Ups Electrical Installation

    C A U T I O N To prevent electrical shock or damage to the equipment, verify that the Powerware 9170 UPS is OFF before you remove the entrance panel. The circuit breaker or disconnect switch must also be off at the AC input service panel.
  • Page 49 Torque the screws holding all input and output power conductors to the values specified in Table 7 on page 39. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 50 UPS Electrical Installation Figure 27 shows input and output wiring terminals inside the Powerware 9170 UPS cabinet. Backplane Board Terminating Studs Figure 27. UPS Input and Output Terminals Wire the UPS for the proper input voltage as shown in Figure 28.
  • Page 51 Figure 29 and Figure 30 describe output wiring configurations for various output voltages. You must also set the operating menu parameter 4-2-4 for the required output voltage as shown in the wiring configuration drawings. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 52 UPS Electrical Installation NOTE For Powerware 9170 UPS models with low-voltage hardwire output, it is recommended to divide the total load as equally as possible between X1 and X2, as shown in Figure 29. NOTE Failure to balance the loads may cause an overload alarm even if the full capacity of the UPS has not been reached.
  • Page 53 3.5 in lb (0.4 Nm). Provide strain relief for cables by installing plastic cable ties. NOTE Do not strain relieve EPO wiring with the same cable tie used for Generator On wires. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 54: System Wiring Diagrams

    L1 – L2 page 43 page 44 page 48 Figure 28b on Figure 30 on Figure 34 on L1 – N page 43 page 44 page 49 *Split-phase power modules required. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 55 External UPS battery cabinets are optional. See “Battery Cabinet Installation” on page 57 for installation instructions. NOTE 6 UPS output circuits shall be installed in dedicated conduit systems and not shared with other electrical circuits. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 56 S 208 Input, 208 Output S 220 Input, 220 Output NOTE 5 S 230 Input, 230 Output S 240 Input, 240 Output Figure 33. No External Bypass (L1, L2), Non-Isolated Output, and Universal Power Modules Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 57 NOTE 6 S 220 Input, 220 Output NOTE 5 S 230 Input, 230 Output S 240 Input, 240 Output Figure 34. No External Bypass (L1, N), Non-Isolated Output, and Universal Power Modules Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 58 UPS Electrical Installation Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 59: Isolated Output Wiring Diagrams

    Chapter 5 Isolated Output Wiring Diagrams The wiring diagrams in this section are unique and specific to installations in which the output of the Powerware 9170 UPS is galvanically isolated from the input. Figure 35 and Figure 36 describe output wiring configurations for various output voltages.
  • Page 60: Neutral-To-Ground Bonding For Isolated Output

    UPS cabinet must have a ground-bond connection for the neutral terminal of an isolated-output system. In such a system, the customer must make the neutral-to-ground (also referred to as N-G or neutral-to-earth) connection after selecting the desired output configuration. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 61 Ground terminations, inside the UPS rear panel, are located directly below the line input terminals. Figure 17 on page 28 shows input and output wiring terminals inside the Powerware 9170 UPS cabinet. If there is any question as to the need for this bond wire, contact your local regulatory agency or your service representative.
  • Page 62: System Wiring Diagrams

    NOTE 10 Do not connect output wiring to X1 when connecting L1 to X3. X1 produces only 88V at 208V nominal output, and 93V at 220V. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 63 S 120/208 Input, 120/240 Output S 110/220 Input, 110/220 Output S 115/230 Input, 115/230 Output S 120/240 Input, 120/240 Output Figure 39. No External Bypass (L1, L2, N), Isolated Output for Single-Phase Voltages Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 64 NOTE 9 NOTE 6 NOTE 9 NOTE 8 S 120/208 Input, 120/208 Output S 127/220 Input, 127/220 Output Figure 41. No External Bypass (L1, L2, N), Isolated Output for Derived 3-Phase Voltages Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 65: Battery Cabinet Installation

    Open the carton containing the external battery cabinet cable assembly. Locate the 3-slot section in the UPS cabinet that contains the power entrance panel. Unscrew and remove the rear panel of this section (see Figure 42). Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 66 Use the pliers to bend the entire breakaway panel (at 3 and 4 in Figure 43) until it breaks away. Figure 43. Breakaway Panel Links Verify all hazardous voltages have been removed from the backplane by testing with a voltmeter or other test device. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 67 Slip the terminals of the cable assembly onto the tabs of the bus-bar extension, putting the tabs between the stud block and the fuse end and between the other stud block and the cable terminal. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 68 If the battery cable will be installed in flexible or other conduit, pull the conductors through the conduit. Attach the conduit to both the UPS power entrance panel and the battery cabinet entrance panel as shown in Figure 46. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 69 Locate the daisy-chained cable on the rear of the first battery cabinet in the section below the location of the first cable assembly. Follow this procedure for connecting any additional daisy-chained battery cabinets. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 70 To UPS or Previous Battery Cabinet To Next Battery Cabinet Figure 47. Connecting Additional Battery Cabinets Reinstall the remaining rear panels using the original screws. Continue to “UPS Startup” on page 63. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 71: Ups Startup

    This UPS contains its own energy source (batteries). The output receptacles may carry hazardous voltage even when the UPS is not connected to an AC supply. When AC input voltage is present, the Powerware 9170 system can provide output voltage even though its batteries are disconnected. To confirm that there is no UPS output voltage, always disconnect all of the AC input sources and unplug all strings of internal battery modules;...
  • Page 72: Power And Battery Module Installation

    (see Figure 48). Repeat for each additional battery module. NOTE All power modules in the Powerware 9170 UPS cabinet must be of the same type: Split-phase power modules have brown labels; universal (single-phase) power modules have black labels. Do not mix brown and black modules in the same UPS cabinet.
  • Page 73: Startup For Plug-Receptacle Units

    Insert the switch key supplied with the cabinet into the button and turn clockwise 1/2-turn. Pull the button out to close the switch. Turn the key back counter-clockwise, and remove the key. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 74 Auto to return to normal Auto mode operation. If applicable, test proper operation of optional external control signals and computer communication before connecting the load. (See “DB-9 Communication Port” on page 90 for details.) Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 75 Failure to balance the loads may cause an overload alarm even if the full capacity of the UPS has not been reached. For Powerware 9170 UPS models with low-voltage output receptacles, it is recommended to divide loads between upper and lower receptacles as equally as possible.
  • Page 76: Startup For Hardwired Units

    At the bypass switch, press the red button and turn the switch to UPS. Remove the six screws in the bypass switch front panel and remove the panel to gain access to the terminal block for voltage measurements. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 77 N to L1 (10 to 11*) 6 to 7* N to L2 (10 to 12*) 6 to 8* *For some installations, there is no connection at terminals 6, 8, 10, or 12. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 78 Insert the switch key supplied with the cabinet into the button and turn clockwise 1/2-turn. Pull the button out to close the switch. Turn the key back counter-clockwise, and remove the key. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 79 Turn on the equipment that is connected to the UPS. If there is an external bypass switch, turn it to UPS. Otherwise, close the load distribution circuit breaker(s). Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 80: Initial Startup Parameters

    Press the <- and -> buttons to move left and right. Press the buttons to increase or decrease the value of each selected digit. When the displayed value is correct, press the button. Set Time time 14:51:38 <- -> Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 81 This setting only affects the alarm; the system continues to operate as an N+X system even if this parameter is left at the default value of 0. Set Redundancy RSetting <- -> Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 82 On/Off function screen. Press the ON button on this screen to start the UPS. These configuration parameters are accessible during normal UPS operation by pressing the Config button through the front panel display. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 83: Operation

    Chapter 8 Operation The Powerware 9170 UPS operates in several different modes. Normally it operates under internal control, called Auto mode, to automatically protect loads connected to it. It also functions under operator control to enable manual override should servicing or testing be required.
  • Page 84 Double Conversion mode of operation. Complete loss of input voltage causes the UPS to transfer to Battery mode. While in H.E. mode, the Powerware 9170 system provides passive EMI filtering in the power path. Off mode turns off the output and most internal circuitry. Within this mode, another mode (Sleep) turns off all internal circuitry when AC line is not present and battery voltage drops to a low threshold.
  • Page 85: Turning The Ups On

    Battery Protect (BP). Sleep mode allows the UPS to remain unpowered for up to six months without having to remove or recharge batteries. Failure to properly power down the Powerware 9170 UPS could permanently damage any installed batteries. Also, if batteries become severely discharged, the UPS might not start immediately when input power is restored.
  • Page 86: Front Panel Display

    Menu/Escape button, for moving into and out of display menus. Also, for avoiding a change to a parameter value. Menu scroll up and down buttons. Also, for increasing/decreasing parameter value digits. Enter button, to activate/accept displayed parameter or operating mode. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 87: Using The Front Panel Display

    M4-B7-12—is shown in the upper right corner of the display. (The count of battery strings does not include additional battery strings contained in connected external battery cabinets.) Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 88 Phase 1 Input Voltage Phase 2 Input Voltage Phase 1 Output Voltage Phase 2 Output Voltage Total System Percent Load Phase 1 Percent Load Phase 2 Percent Load Battery Voltage Estimated Battery Run Time Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 89: Parameters

    Operation Parameters The parameters describe the Powerware 9170 system operation. Some useful parameters are input and output voltage, input and output current, and battery voltage. The UPS measures or records many other parameters. Some are operator-adjustable, such as the local date and time and various operating limits. All parameters are password-protected.
  • Page 90: Inverter Log

    Table 11. Inverter Log Messages Message Explanation Line Fault UPS switched to battery because the input voltage was too high or too low. Battery Test Battery test initiated inverter operation. Manual Operator initiated inverter operation. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 91: Alarm Log

    Figure 58. Alarm Log Entry In Figure 58, the sixth most-recent alarm (2 2 6) is being displayed. “A” means the Powerware 9170 system sounded alarm A (Low Battery). If the alarm is still active, an asterisk (*) is displayed beside the letter alarm code.
  • Page 92: Battery Test

    3 1 1. When the test is complete, the UPS automatically provides the results on the screen. Menu Map Figure 60 is an illustration of how to access all Powerware 9170 system parameters. The menu structure has 6 primary-level menus, named System Status Menu (1) through Service Menu (6).
  • Page 93 5 System ID 5 1 Time 5 2 Date (ESC) 5 3 Model Name 5 4 Serial Number 5 5 Software Version 6 Service Menu (Top) Figure 60. Powerware 9170 System Menu Map Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 94 Operation Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 95: Communication

    It also gives you a complete record of critical power events, and it notifies you of important UPS or power information. If there is a power outage and the Powerware 9170 system battery power becomes low, LanSafe software can automatically shut down your computer system to protect your data before the UPS shutdown occurs.
  • Page 96: Communication Slots

    The ConnectUPS-BD card also allows UPS-dependent computer systems to automatically shut down during extended power outages using the NetWatch client software provided on the Powerware Software Suite CD or Web site. Relay Interface Card (BestDock Model) The BestDock Relay Interface Card provides true relay contact output to peripheral devices.
  • Page 97 These parameters are also available to trained service personnel through the Service Menu. See Figure 15 on page 26 and Figure 21 on page 31 to make the connection for all dedicated input signals. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 98: Db-9 Communication Port

    Communication DB-9 Communication Port Table 13 explains the functions of the pins on the Powerware 9170 DB-9 communication port. This port is on the Powerware 9170 UPS rear panel, as shown in Figure 49 on page 66. Table 13. DB-9 Port Signals...
  • Page 99: Maintenance

    Nevertheless, the Powerware 9170 UPS and optional external battery cabinets do require some attention to assure continued reliable service. The service technician should follow Powerware’s recommended maintenance schedule, which includes the following items: Check operating environment for clean, cool, dry conditions.
  • Page 100: Storage Temperature

    (in the UPS or external battery cabinet) at –20 to +40 ° C (–4 to +104 ° F). Batteries will have a longer shelf life if they are kept below +25 ° C (+77 ° F). The Powerware 9170 UPS or battery cabinet without batteries may be stored at –40 to...
  • Page 101: Battery Replacement

    Maintenance Battery Replacement The Powerware 9170 hot-swappable feature allows you to replace the battery modules easily without disconnecting the load or damaging the batteries. NOTE The Powerware 9170 UPS will operate with uncharged (or no) batteries, but will have limited (or no) battery backup capability. Backup protection requires at least three battery strings for every four power modules.
  • Page 102: Power Module Replacement

    Maintenance Power Module Replacement The Powerware 9170 hot-swap feature allows you to replace a power module easily without disconnecting the load or damaging the UPS. NOTE The UPS may switch to internal bypass if the remaining power modules are insufficient to supply the required power. If empty slots exist, install replacement modules before removing original ones.
  • Page 103: Specifications

    Chapter 11 Specifications This section provides the following specifications for the Powerware 9170 models: Electrical input and output Isolation Model specifications Environmental and safety Battery Weights and dimensions Table 14. Electrical Input and Output Nominal Input Voltage 200–240 Vac or 100/200, 110/220, 120/208, 120/240, 127/220 Vac Input Voltage Range 176–276 Vac*...
  • Page 104 Isolation, Including Output Code Article 250-5d, with output neutral bonded to ground. No direct connection between input and output; neutral-to-ground bond is Neutral-to-Ground Bonding required; other local codes may take precedence. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 105 *In High-Efficiency and Bypass modes the input current equals the output current plus 2A for each power module in the system. For redundant power module operation (N+X), increase the input current rating by 2A for each additional redundant power module. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 106 *In High-Efficiency and Bypass modes the input current equals the output current plus 2A for each power module in the system. For redundant power module operation (N+X), increase the input current rating by 2A for each additional redundant power module. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 107 *In High-Efficiency and Bypass modes the input current equals the output current plus 2A for each power module in the system. For redundant power module operation (N+X), increase the input current rating by 2A for each additional redundant power module. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 108 *In High-Efficiency and Bypass modes the input current equals the output current plus 2A for each power module in the system. For redundant power module operation (N+X), increase the input current rating by 2A for each additional redundant power module. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 109 Ventilation The air around the UPS must be clean and free of dust, corrosive chemicals, and other contaminants. The Powerware 9170 UPS uses internal fans to circulate the air for cooling. The air must be free to circulate around the UPS and battery cabinet(s).
  • Page 110 12-slot cabinet: 275 lb (125 kg) Optional floor anchor kit weighs 9 lb (4 kg) Each battery module weighs 30 lb (14 kg) Each power module weighs 17 lb (8 kg) Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 111: Troubleshooting

    See the instructions accompanying the LanSafe III software CD-ROM. software? Check the input or output Go to menus 1-1-2 and 1-1-3 for the input voltage; go to menus 1-2-2 and voltage? 1-2-3 for the output voltage. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 112 When the display shows Auto High Efficiency, press the button. Set the UPS to operate in The Powerware 9170 system will not change operating modes as a timed High Efficiency mode on event. But, if you wish to conserve energy, before leaving for the weekend, go weekends? to menu 4-1.
  • Page 113: Alarms

    (Silence) (Clear) (ESC) Figure 62. Detailed Alarm Entry When the Powerware 9170 UPS detects an alarm condition, the UPS displays the alarm with the following indications: the red LED next to the front panel display illuminates sounds an audible alarm...
  • Page 114 The load is requiring more power Switch off your equipment one piece at a time than the UPS power modules are until the alarm stops. capable of supplying, and the UPS has switched to Bypass mode. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 115 Contact your service Incompatible Module installed in the system. representative. 5 Fan Failure The UPS has detected a module Contact your service representative. fan problem that requires service. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 116 Reduce the load or install additional power Redundancy is too few to provide the programmed modules. redundancy level while protecting the Insufficient load. The UPS will protect the load, Modules but will not be fault tolerant. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 117: Service And Support

    A replacement or repair unit will be shipped, freight prepaid for all warrantied units. NOTE For critical applications, immediate replacement may be available. Call the Help Desk for the dealer or distributor nearest you. Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...
  • Page 118 Troubleshooting Powerware 9170 UPS User’s Guide Rev B www.powerware.com ®...

Table of Contents