Creating The Alarm Texts Via Win128 - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
13.20.1
The display Ext. FBPs 1826
1735 & 1736 and the Ext. Presentation unit 1728:
information as in EBL128 will be shown, if no other alarm text has
been programmed, see below.
Presentation number
When an alarm point is activated, both the zone number and the
address (ZZ-AA) will be shown.
When a zone line input (e.g. on a 4580 board) is activated, only the
zone number (ZZ) will be shown.
See also EBL128 Operating Instructions, chapter "Fire alarm".
Alarm text
User definable alarm texts with up to 40 alphanumeric characters are
created and downloaded via Win128.
Each addressable alarm point and each zone can have an individual
alarm text shown in EBL128 and the same or another alarm texts
shown in each Ext. FBP 1826 / 1828, Alert Annunciation unit 1735 /
1736 and Ext. Presentation unit 1728, since specific texts can be
downloaded in each unit individually.

Creating the alarm texts via Win128

Information is also available via Win128 help.
In the dialog box for an alarm point (e.g. a detector)
"Text" field where the alarm text for the alarm point can be typed (or
edited). This is the text that will be shown in the display in EBL128
when this alarm point has activated a fire alarm.
Alarm text
The alarm text can as an alternative be typed (or edited) in the Win128
"Text editor" (menu Tools | Edit Alarm Texts...).
No matter where the text is typed, it will be shown on both places.
110
The information will also be printed if a printer is available in the ext.
FBP 1826.
111
For maximum number of texts, see chapter "Limitations", page 144.
112
In Win128.
100
EBL128 Planning Instructions V1.1.x
110
& 1828, the Alert Annunciation units
111
See also Win128 help.