Input Units - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
6.1.1
The following units (in NORMAL mode) can be connected to the
COM loop:
Address setting / Technical address
Each COM loop unit has to have a unique technical address (001-
127). This address and the mode are set with an Address Setting Tool
3314. For EBL128 is always the NORMAL mode used (default).
NOTE!
The technical address for Addressable Base station for
wireless units is set on a DIL-switch in the unit respectively.
The technical address for a wireless detector is depending on which
Base station it is "connected" to, see chapter "Other COM loop units",
page 44.

Input units

Each COM loop input unit is added and programmed via Win128.
Depending on type of unit, regarding:
Technical address (001-127)
Name (normally not changed)
Zone number and Address within the zone
Two-units-dependent fire alarm, i.e. co-incidence alarm (if you
wish / some units only)
Quiet alarm or not (Australian function)
Alert annunciation & Time Channel (if you wish / some units
only)
Disablement & Time Channel (if you wish / some units only)
Alarm text (if you wish)
Regular Alarm algorithm (some units only)
Alternative Alarm algorithm & Time Channel (if you wish / some
units only)
EBL128 Planning Instructions V1.1.x
and 3339)
and 3379)
31