Interlocking Indications; Information Of Interlocking Combinations (H9); Display Interlocking Information (H9/C1) - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
11.2
11.3
11.3.1
Latched output checked = Output reset has to be performed via menu
H9/C3. (Automatically output reset will not take place when the
control expression becomes false.).
Fault checked = Fault detection ON.
Fault Detection Time: If the input is not activated within 5-255
seconds after the output is activated
FAULT: Interlocking input AA/PP
Date: MM-DD

Interlocking indications

One or more activated Interlocking Combinations (interlocking output
and/or input) are indicated in the display in EBL128
Interlocking input/output activated
See menu H9/C1
Disabled interlocking output is indicated by the LED "Disablements".
Information of interlocking combinations
(H9)
Menu H9 has the following sub menus.

Display interlocking information (H9/C1)

See also chapter "Interlocking indications", page 78.
In menu H9/C1 information will be shown as follows:
Output AA/PP activated at HH:MM
Interlocking text.. .. ..
or
Output AA/PP act HH:MM, input act HH:MM
Interlocking text.. .. ..
or
Input AA/PP activated at HH:MM
Interlocking text.. .. ..
AA = Interlocking combination Area
PP = Interlocking combination Point within the Area
HH = Hours
MM = Minutes
Use "↑" "↓" to scroll between several interlocking combinations.
83
After the end of the delay time (if used).
84
This indication has low priority and will only be shown in the display if
there are no fire alarms, faults, disablements, etc.
EBL128 Planning Instructions V1.1.x
83
, a fault will be generated:
Time: HH:MM
77