Time Channels 1-4; Time Channels 5-12; Event Log; Loss Of Main Power Source - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
13.22
13.23
13.24
13.25

Time channels 1-4

Time channels 2-4 are controlled by the EBL128 RTC (real time
clock). One time on, one time off, one time on and one time off can
be set for each time channel 2-4.
For time channel 1 can no times be set. Default is "Always off" and
"Always on" can be selected.
The time channels 1-4 can be used to:
disable and re-enable alarm points / zones
turn ON (enable) / OFF the Alert Annunciation function
activate programmable control outputs
turn ON (enable) / OFF the alternative alarm algorithm for analog
detectors
The properties for each Time channel (2-4) and each Day (Monday –
Sunday + National Holiday) have to be set, see chapter "Time
Channels", page 119.

Time channels 5-12

Time channels 5-12 are controlled by some external device via a
116
programmable input.
disable and re-enable alarm points / zones
turn ON (enable) / OFF the Alert Annunciation function
activate programmable control outputs
turn ON (enable) / OFF the alternative alarm algorithm for analog
detectors
One programmable input ("Time Channel N") can control one time
channel. The input has to be controlled by some external device, e.g.
another time system, a key switch, a timer, etc. with a normally open
or a normally closed contact.
channel is turned ON.
NOTE! Do not use more than one input per time channel.

Event log

150 events will be stored in a circular log, i.e. the log re-starts when it
is "full". The log shows the 150 latest events.
The event log can be shown via menu H4/U5 or shown / printed via
Win128.
Date & Time are stored together with every event.

Loss of main power source

Regarding the Main power source and Second power source, see
chapter "Power supply", page 137.
116
One programmable input per time channel.
117
Normally low or a normally high for an optocoupler input.
103
EBL128 Planning Instructions V1.1.x
Time channels 5-12 can be used to:
117
When the input is "activated" the time