Programmable Inputs - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
7

Programmable inputs

EBL128 has one programmable input (I0). In EBL128 can also be
mounted the Inputs and Outputs expansion board 4583, with five
programmable inputs (Input 0-4). See chapter "Expansion boards
458x", page 22. All these inputs can be supervised or not supervised.
On the COM loop can be connected up to 16 addressable multi
purpose I/O units 3361
inputs (In0/Z and In1), not supervised.
Each input is programmed (via Win128) regarding:
Name (Normally not changed, but used as Interlocking input it is
recommended to add some identification information)
Type ("Trigger condition")
Not supervised or Supervised. (Not valid for 3361.)
Logic, Normally open (high resistance, 3K3, when supervised) or
Normally closed (low resistance, 680R, when supervised)
Ext. Fault (Text; only for trigger cond. "External fault")
Ext. time channel Name (only for trigger cond. "External time
channel")
Activate output (Technical address and Output)
Zone, Address and Text (only for trigger cond. "General fire",
"Pre-warning" and "Zone line input").
Alert Annunciation time channel (only for trigger cond. "Zone
line input" – 3361 In 0).
Disablement time channel (only for trigger cond. "Zone line
input" – 3361 In 0).
Figure 10. The Win128 "Input" dialog box. The different trigger
conditions ("Type") require different additional information.
56
Units type 3361 + 3364 = max. 16.
EBL128 Planning Instructions V1.1.x
56
. Each 3361 unit has two programmable