Advanced; Main Power Loss Fault; Alarm Reset; Door Closing By Time - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
16.6
16.6.1
16.6.2
16.6.3

Advanced

Figure 32. The Win128 tab page "Control Unit Properties" with
the tab "Advanced" open.

Main power loss fault

Delay time: A fault will be activated 0 – 300 minutes after loss of
mains (230 V AC). Default is 30 minutes.
NOTE! More than 30 min. is a violation to the EN54-2 standard.

Alarm reset

One of the following alternatives shall be selected.
 Multiple reset (default): Fire alarms will be reset all at the same
time by pressing the "Reset" button.
 Single encapsulated reset: Fire alarms will be reset one by one
by pressing the "Reset" button. The fire alarm shown on the first
row to the left in the EBL128 display will be reset. This function
is a violation to the EN54-2 standard.
Encapsulation function: If an alarm point is reset while still in
alarm state (e.g. an activated manual call point), this unit will be
automatically disabled
H2/B5. Before re-enabled, no fire alarm can be activated by this
alarm point. This function is a violation to the EN54-2 standard.

Door closing by time

Can be selected / set when the "Fire door closing" function (ABDL) is
used, see chapter "Fire Door Closing function", page 80.
Active: This checkbox shall be marked if the fire doors shall be
closed at a definite time (HH:MM) every day.
131
Indicated by LED "Disablements".
124
EBL128 Planning Instructions V1.1.x
131
and will be so until re-enabled via menu