16.2
Investigation time: 3 min.
3 is default. 1-9 minutes is possible to set.
NOTE! According to EN54-2, the total delay of fire alarm routing
equipment must not exceed 10 minutes, i.e. Acknowledge time +
Investigation time < 10 minutes.
Multiple alarms allowed within same zone
Checkbox unmarked (default): Alert annunciation alarm activated
by only one alarm point within the same zone is allowed.
Checkbox marked: Alert annunciation alarm activated by two or
more alarm points within the same zone is allowed.

Time Channels

Figure 25. The Win128 tab page "Control Unit Properties" with
the tab "Time Channels" open.
Regarding time channels, see chapter "Time channels 1-4", page 104.
For Time channel "1" can no times be programmed. Default it is
"Always off" and "Always on" can be selected.
For time channel 2-4 programming, select a time channel in the list (to
the left) and click "Properties.
127
Alarm from two or more alarm points within the same zone will activate
normal fire alarm, i.e. the "Fire brigade tx" output will be activated.