Units Connected To The Rs232 Interface J5; Web-Servers - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
6.3
6.3.1
are in German. Serial RS485 interface for IHD protocol.
The unit is power supplied from EBL128 (or an ext. power
supply). Up to 1200 m cable can be used.
NOTE! Switch 1 on the DIP switch shall be set to "on".
FAT 2002 German Fire Brigade Indicator Panel (Feuerwehr-
Anzeigetableau). A grey metal housing (HxWxD, 185 x 255 x
58 mm) with a door. A key is required to open the door, which
has a Plexiglas ahead of the front. It has cable inlets on the top,
bottom and back sides and is intended to be wall mounted.
The function, Display information, LED indicators and push
buttons on the front are in accordance with DIN 14662. The
front's designation texts are in German.
interface for IHD protocol.
The unit is power supplied from EBL128 (or an ext. power
supply). Up to 1200 m cable can be used.

Units connected to the RS232 interface J5

Web-servers

1598
Web-server II. This unit has replaced 1588 and can be used:
a) for presentation of the actual c.i.e. status in a PC using the
web browser Microsoft Internet Explorer. It can also send e-
mails in case of pre-warning, fire alarm, fault, disablement,
test mode alarm and/or service signal.
b) for remote control with encrypted and safe two-way
communication and five different user (access) levels.
c) as a gateway to other PC systems etc. Three alternatives
are available today:
c1) EBL Talk is an open protocol, used to transmit and
present fire alarm information in a separate PC / system.
c2) Tateco, used to transmit and present fire alarm
information in an Ascom Tateco paging system.
c3) SIA, used to transmit and present fire alarm
information in a separate PC application.
A PC tool, Web128 II Config tool is used for the
configuration, which is downloaded to the web-server via
TCP/IP.
The Web-server II consists of a light grey plastic cabinet
(90x25x69.5 mm), which shall be vertically mounted on the
symmetric 35 mm DIN rail in the EBL128 c.i.e.
Web-server II has the following interfaces:
RS232 to connect the web-server to J5 in the EBL128 c.i.e.
RS232 to connect the web-server to other PC / system
RJ45 (10 BASE-T) to connect the web-server to Internet / an
intranet (LAN)
Molex 3.5 to connect the web-server to a power supply (24 V
DC, max. 65 mA), e.g. to J4 in the EBL128 c.i.e.
EBL128 Planning Instructions V1.1.x
50
Serial RS485

Advertisement

Table of Contents
loading