Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
8.2
EBL128.
The following fault message will be shown:
FAULT: Charging ext. power supply
14. "Fire door closing" outputs will be activated for 20 seconds by
this trigger condition.
15. Pre-warning, e.g. from a High Sensitive Smoke Detector's pre-
warning output. Zone no. and Address set to the same as the
corresponding fire alarm (from the same detector).
16. "Activated Fault routing equipment" signal (feed-back) to
EBL128 will light up the LED "Fault tx activated" on the front.
Output with trigger condition "Indication Fault tx Activated" will
be activated.
17. Activated input will light up the LED "Extinguishing" on the
front. (Normally the LED will be lit when a corresponding output
is activated.) Output with trigger condition "Extinguishing system
released" will be activated.
18. Activated input will generate a fault in EBL128. Output with
trigger condition "Extinguishing system fault" will be activated.
The following fault message will be shown:
FAULT: Extinguishing system fault
19. Activated input will activate a fire alarm in EBL128 (Zone no.)
from an extinguishing system. The alarm devices will not be
silenced by the "outside switch" (New Zealand FB Silence
switch).
20. Activated input will generate a fault in EBL128.
The following fault message will be shown:
FAULT: Fault warning routing equipment
21. Activated input will activate an output (Technical address /
output.)
22. Used for the "outside switch" (i.e. the New Zealand FB Silence
switch).
23. Output with trigger condition "Activated Key cabinet" will be
activated.
24. Activated input will activate all programmable outputs of type
"Alarm devices" steady (continuous).
25. The Addressable multipurpose I/O unit 3361 monitored input
"In0" used as zone line input (Z) for conventional detectors.

Logic

The logic has to be set (in the Win128 dialog box "Input Properties").
EBL128 Planning Instructions V1.1.x