Troubleshooting With Indicator Displays - Omron WT30 Operation Manual

Fa wireless ss terminal
Hide thumbs Also See for WT30:
Table of Contents

Advertisement

Troubleshooting
5-1-2

Troubleshooting with Indicator Displays

MS and WS Indicators
Serial Master Station Indicators
Indicator
(1) PWR
(2) COMM
(3) MS
(Module Status)
(4) WS
(Wireless Status)
(5) RSSI (Received Signal
Strength Indicator)
70
The status of the MS and WS indicators depends on the communications sta-
tus, as follows:
The MS (Module Status) indicator shows the status of the local node.
The WS (Wireless Status) indicator shows the status of the wireless system.
During normal operation these two indicators are lit green on both the Serial
Master Station and the I/O Slave Stations.
(1)
(2)
PWR
COMM
Color
Status
Green
Lit
Not lit
Yellow
Lit
Not lit
Red
Lit
Flashing
Green
Lit
Flashing
---
Not lit
Red
Lit
Flashing
Green
Lit
Flashing
---
Not lit
Red/yellow/
0 to 9 lit
green
Green
Flashing
(3)
(4)
1
MS
WS
Meaning (primary error)
Power is being supplied.
Power is not being supplied.
Serial communications in progress.
No serial communications.
A fatal error has occurred that cannot be recovered from, such
as a watchdog timer error, EEPROM, or hardware error.
Replace the WT30 Terminal.
A non-fatal error, illegal switch settings, or EEPROM checksum
error has occurred that can be recovered from by resetting the
system.
Communications are normal.
TEST mode or SET mode has been activated.
Power is not being supplied or the system is resetting.
A fatal wireless communications error or code sense error has
occurred.
A non-fatal wireless communications error or verification error
(slave I/O size mismatch) has occurred, or the slave is not regis-
tered.
RUN mode: Connection to wireless communications is com-
pleted or remote I/O communications are in progress.
SET mode: Scan list creation completed.
RUN mode: There is no wireless communications connection or
there are no slaves participating in remote I/O communications.
TEST mode: The received signal strength is being monitored.
SET mode: Scan list is being created.
Wireless communications are not in progress.
Displays the received signal strength in 10 levels. The field
strength is determined by the number of indicators lit: weak for a
small number and strong for a large number.
Special function operation has completed.