Registering the Communications Partner
Received Signal Strength Indicator
Field strength
Number of indicators lit
RUN mode
TESTmode
Field strength monitor
test
Installation/confirmation test
3-5
Registering the Communications Partner
2. Confirm that the MS and WS indicators on the Serial Master Station are lit
green.
MS: Module status indicator
WS: Wireless status indicator
MS
WS
3. Specify the node number of the I/O Slave Station to be monitored on the
Serial Master Station's node setting switch.
W NODE
X10
X1
Note The Serial Master Station node number is set to the maximum
number of I/O Slave Stations. When the maximum number of
nodes is set to a number higher that the number of nodes connect-
ed, however, the highest node number is not used. The communi-
cations partner for this node number does not exist, so no display
is shown on the RSSI. If the node number is changed to that of a
node that is actually connected, the RSSI display will indicate the
corresponding signal strength.
4. Check the strength of the received signal from the I/O Slave Station spec-
ified by the node setting switch. The strength is indicated using 10 levels
on the RSSI display.
Red indicators
Weak
0
1
2
Unstable communications range
Range in which
specified channel
can be used.
Unstable communications range
The received signal strength is indicated using 10 levels. Check the communi-
cations status, referring to the field strength level.
Use the following procedure to operate a system configured with a Serial
Master Station and either a PLC or personal computer connected via RS-
232C in which the I/O Slave Stations have been registered.
Setting range: 01 to 64
Few
Number of LEDs lit:
Field strength:
Weak
Yellow indicators
Medium
3
4
5
Stable communications range
Range in which specified channel cannot be used.
Stable communications range
Section 3-5
Many
Strong
Green indicators
Strong
6
7
8
9
45