Connections
Dust-proof Label
Attaching Terminal Labels
(I/O Slave Stations Only)
2-2-3

WT30 Power Supply Wiring

• Wire the terminals using the following post terminals and cables.
10 mm
Length of exposed wire
Use a tool of the appropriate size to crimp the post terminal. Make an incision
in the cable and remove the covering so that the cable is either the same
length as or approximately 0.5 mm longer than the post terminal, as shown in
the following diagram. Make sure that no stray wires are protruding and the
post terminal is not damaged.
Correct Example
0 to 0.5 mm
Incorrect Example
Surface damage
Stray wire
Insufficient length
removed
Insert a screwdriver into the screwless terminal block as shown in the follow-
ing diagram, and keeping the screwdriver inserted, insert the post terminal.
Use the same procedure to remove the post terminal. Secure the wiring close
to the connector to prevent direct force from being applied to the wiring due to
twisted cables or the weight of the cables.
Remove the dust-proof label after completing wiring.
W T3 0-
M 01 -F
LK
Attach terminal labels inside the switch cover to the positions shown in the fol-
lowing diagram.
0 1 2 3 4 5 6 7
IN
8 9 10 11 12 13 14 15
ANT1
PWR
ERR
MS
WS
1
W NODE
W CH
MODE
RUN
TEST
x10
x1
x10
x1
SET
ON
FUNCTION
The power supply voltage for WT30 Terminals is 24 VDC.
Cable (AWG22 to AWG16)
single/stranded wire (0.32 to 1.5 mm
Manufactured by Phoenix Contact
Post terminal
Crimping tool
ANT2
RSSI
9
ENTER
ON
OFF
Section 2-2
2
)
AWG22
AI 0.34-12
AWG20
AI 0.5-10
AWG18
AI 0.75-10,
AI 1-10
AWG16
AI 1.5-10
CRIMPFOX ZA3