Connecting The Power Supply - Omron NS8-TV0-V2 Setup Manual

Programmable terminals
Table of Contents

Advertisement

3-1 Installing the PT
3-1-4
3-6
Downloaded from
Elcodis.com
electronic components distributor
AC
Reference
For the NS15 to provide IP65 oil-proof-type protection, at least the eight locations
shown in the following figure must be mounting with mounting brackets. There is a total
of 16 mounting locations.

Connecting the Power Supply

Connect a 24-VDC power supply to the power input terminals.
• Do not connect an AC power supply to the power terminals.
Precautions
• Use a DC power supply with low voltage fluctuation.
for Safe Use
• Do not perform a dielectric strength test.
• To conform to EC Directives, use a DC power supply that will provide a sta-
Power Supply
The following table shows the specifications for the power supply that can be connected. De-
termine power supply specifications that meet the power supply capacity requirements.
Item
Power supply voltage
Allowable voltage range
Power supply capacity
DC power
Line
supply
24 VDC
ble output even if the input is momentarily interrupted for 10 ms, and that
has reinforced or double insulation.
Value
24 VDC
20.4 to 27.6 VDC (24 VDC ±15%)
45 W min. (NS15)
25 W min. (NS12, NS10, NS8)
15 W min. (NS5)
Noise Filter
Load
PT
TAH-06-683
(Functional
ground)

Advertisement