Section 5 Troubleshooting and Maintenance
NS Series Programming Manual
Message
Time-out error occurred while
writing due to the following:
Disconnection of the connecting
cable
Stopped host_- Incorrect
time-out period
Allocation Host: XXXX
Do you want to retry?
NS5:
Time-out error occurred while
writing to the System Memory
Area.
Allocation Host: XXXX
Do you want to retry?
Communication error
detected while writing by the
following case:
Corrupted data by noise
Transmit error by the host
Allocation Host: XXXX
Do you want to retry?
NS5:
Communication error detected
while writing to the System
Memory Area
Allocation Host: XXXX
Do you want to retry?
Communication error
detected while writing by the
following case:
Corrupted data by noise
Transmit error by the host
Allocation Host: XXXX
Do you want to retry?
NS5:
Communication error
detected while writing to the
System Memory Area.
Allocation Host: XXXX
Do you want to retry?
Addressing error exists in the
screen, alarm, data log, or
macro. Correct address setting
by the CX-Designer.
Screen No.: XXXX
Allocation Host: XXXX
Allocation Address: XXXX
NS5:
Addressing error exists in the
screen, alarm, data log or
macro.
Screen No.: XXXX
Allocation Host: XXXX
Allocation Address: XXXX
Cause
The communications
cable is not properly
connected. The host
communications
service has stopped.
The timeout monitoring
time is too short.
Data corrupted by
noise
Invalid host communi-
cations command
Data corrupted by
noise
Invalid host communi-
cations command
The storage type of the
number set for a func-
tional object does not
match the data type of
the tag.
Settings are made to
monitor data that ex-
ceeds the maximum
number of elements for
an array variable.
5-33
Possible countermeasure
Check the cable connection and conduct a
continuity test. Replace the cable if there is a
cable error, or rewire the cable if necessary.
Check the cable connection and conduct a
continuity test. Replace the cable if there is a
cable error, or rewire the cable if necessary.
Check the cable connection and conduct a
continuity test. Replace the cable if there is a
cable error, or rewire the cable if necessary.
Change the settings using the CX-Designer.
Alternatively, change the host tag settings.
5-2 Error Messages