Troubleshooting Errors During System Menu Operation - Omron NS Programming Manual

Ns-series programmable terminals
Hide thumbs Also See for NS:
Table of Contents

Advertisement

Section 5 Troubleshooting and Maintenance
NS Series Programming Manual
5-2-6

Troubleshooting Errors during System Menu Operation

Message
Error occurred while formatting
screen data range.
Failed to save to a file.
The address set at CH type se-
lection is not correct. Check the
address and input the correct
address again.
Allocated host: XXXX
Allocated address: XXXX
MRES = XXXX, SRES = XXXX.
Time-out error occurs while
downloading by the following
case:
Disconnection of the connect-
ing cable
Stopped host
MRES = XXXX, SRES = XXXX.
NS5:
Time-out error occurs while
downloading Host
Allocated host: XXXX
The address set at CH type
selection is not for writing.
Check the address and input the
correct address again.
Allocated host: XXXX
Allocated address: XXXX
MRES = XXXX, SRES = XXXX.
Other peripheral tool is access-
ing. Send commands again after
access right is released.
Allocated host: XXXX
Allocated address: XXXX
MRES = XXXX, SRES = XXXX.
Communication error detected
while downloading by the
following case:
Corrupted data by noise
Transmit error by the host
MRES = XXXX, SRES = XXXX.
NS5:
Communication error detected
while downloading the data
Allocated host: XXXX
Registered host information and
communication setting are not
match. Check the communica-
tion setting.
Destination address is incorrect.
Check the host information.
Cause
Hardware failure.
File system damaged.
Set address is incorrect.
Cable is disconnected.
PLC power supply is OFF.
Host is in RUN mode.
Tried to write to a write
prohibited address.
CX-Programmer or other
programming device is
connected.
Data corrupted by noise.
Invalid host communications
command.
Registered host selected but
not connected.
The remote address where
the host is registered is
incorrect.
Connected to a different PLC
while online.
5-16
5-2 Error Messages
Possible countermeasure
Contact your nearest OMRON representa-
tive.
Format the screen data area and transfer
the screen data again.
Check whether or not an illegal address
has been set and set the correct address.
Connect the cable correctly.
Turn ON the PLC power supply.
Change to program or monitor mode.
Check the address and set the correct
address.
Disconnect the connected programming
device.
Check the cable connection and conduct a
continuity test. Exchange the cable if there
is a cable error. If necessary, rewire the
cable.
Change the communications settings
under the System Menu so that the
corresponding port is set.
Check the host registration and, if neces-
sary, use CX-Designer to change the
address.