Omron GRT1-ML2 Hardware Reference Manual page 151

Trajexia motion control system
Hide thumbs Also See for GRT1-ML2:
Table of Contents

Advertisement

Hardware reference
LED
Description
Color
TS
SmartSlice I/O
N/A
system com-
munication
status
Green
Red
UNIT
Green
PWR
I/O PWR
Green
HARDWARE REFERENCE MANUAL
Status
Meaning
Not Lit
No power supply
Communication with SmartSlice I/
O Unit has not started
Overcurrent detected
Flashing
SmartSlice I/O Unit added to the sys-
(every
tem
second)
Flashing
Backup/Restore function operating:
(every 0.5
Restoring settings to SmartSlice I/
second)
O Unit, backup function operating
Downloading SmartSlice I/O Unit
settings
Lit
Communication with SmartSlice I/O
Unit established
Flashing
Non-fatal communication error
occurred.
Communication timeout
Verification error occurred with
registered table
Different model unit detected after
SmartSlice I/O Unit replacement
Lit
Fatal communication error occurred.
Lit for 2 s
Failure occurred while restoring set-
tings to I/O unit or downloading I/O unit
settings
Not Lit
No power supply to the unit
(All LEDs are off)
Lit
Power supply to the unit
Not Lit
No power supply to the SmartSlice I/O
(No output from the SmartSlice I/O
Units, even when they are in operation)
Lit
Power supply to the SmartSlice I/O
Note
When the power of the Trajexia system is turned on, the TJ1-
MC__ executes its startup sequence before it initializes the
MECHATROLINK-II bus. During this startup sequence, the ML
COM LED is off.
When the TJ1-MC__ initializes the MECHATROLINK-II bus
with the command MECHATROLINK(unit,0), the ML COM
LED goes on.
When the GRT1-ML2 loses the MECHATROLINK-II communi-
cation with the master, or when the command
MECHATROLINK(unit,1) is executed, the ML COM LED goes
off.
Communication dipswitches
/i
Dipswitch
Function
1
MECHATROLINK-II
address range
2
MECHATROLINK-II
bus speed
3
Frame size
4
HOLD/CLEAR
1. Trajexia only supports 10 Mbps bus speed. Therefore always set
dipswitch 2 to OFF.
2. Trajexia only supports 32-byte communication. Therefore always set
dipswitch 3 to OFF.
Setting
Description
70 hex − 7F hex
ON
60 hex − 6F hex
OFF
1
OFF
10 Mbps
2
OFF
32 bytes
ON
HOLD: All outputs hold their values
when communication is lost
OFF
CLEAR: All outputs become 0 when
communication is lost
146