Ekip Dip

1 - Operator interface

Introduction The operator interface of the Ekip Dip protection release allows you to:
Components of the interface The Ekip Dip operator interface appears as follows:
21 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
• Set the parameters relating to the available protections.
• View the status of the trip unit and alarms.
• Connect to the frontal connector to communicate and perform the opening test.
Figure 5
The following table provides a description of the components of the interface:
Position
Type
A
B
C
LED
D
E
F
G
H
Protections:
thresholds
I
L
M
Protections: times
N
O
P
Settings
Q
Test
R
IMPORTANT: the figure above refers to an Ekip Dip, LSIG version. In the case of Ekip Dip
LI or LSI versions, LEDs and dip-switches related only to the protections present are
available.
LED The LEDs are useful on Ekip Dip in order to distinguish and identify various types of information on the
protection trip unit, the circuit-breaker and state of the line currents.
Operational conditions
The operation of the LED is determined by the power supply conditions of the trip unit:
• With the trip unit energized (by current sensors or by auxiliary power supply or by Ekip TT or by
Ekip T&P) the LEDs are operational for all the signals.
• With the trip unit de-energized, the LEDs are limited to the signalling of the last switch-off or trip
event (combined with the check via iTest, described below).
Description
L Protection LED (alarm and trip)
L Protection LED (pre-alarm)
S Protection LED (alarm and trip)
I Protection LED (trip)
G Protection LED (alarm and trip)
Power-on LED (trip unit powered and on)
L Protection dip-switch (threshold I1)
S Protection dip-switch (threshold I2)
I Protection dip-switch (threshold I3)
G Protection dip-switch (threshold I4)
L Protection dip-switch (time t1)
S Protection dip-switch (time t2 and type of curve)
G Protection dip-switch (time t4 and type of curve)
Neutral and frequency dip-switch
Test pushbutton
Test connector
ABB | SACE Emax 2
Continued on the next page
Ekip Dip
1 - Operator interface