ABB SACE Emax 2 Series Operating Instructions Manual page 295

Low voltage air circuit-breaker
Table of Contents

Advertisement

292 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Continued from the previous page
IEEE 1588 synch
Synchronization problem of IEEE 1588 synchronization reference module
Ekip Com module detected with incorrect / not allowed MAC address,
MAC Address
contact ABB.
Ekip Installation
Installation error between HMI and Mainboard, contact ABB
Install Measurement module ( Settings-Circuit breaker-Installation-
Measuring installation
Measuring-Install ) menu
Install Rating Plug ( Settings-Circuit breaker-Rating Plug-Install menu) and
RatingPlugInstallation
check connection if there are further faults
Maintenance alarm: carry out maintenance and then reset the alarm via
Maintenance
Ekip Connect (see 1SDH001330R1002)(see page116)
The average power limit setting of the Power Controller has been
PC Power exceed
exceeded
Rating plug not present, value or size incompatible with Ekip Touch
Rating plug
parameters
Zone Selectivity Diag
Error in zone selectivity connections (Hardware Selectivity)
S.G.R. Toroid
Check connection and state of toroid
Fault in connection of sensors to Trip unit; check status of sensors,
including external Neutral, or call ABB
Sensor L1/L2/L3/Ne
Check current sensors, status of terminal and cables connecting to Ekip
Touch
TFTP server enabled and/or configuration session open on module Ekip
Configuration Session
Com IEC 61850 or Ekip Hub
value (condition in which the Power LED flashes)
• After having pressed and held the Trip unit test button for at least three
seconds
__logo__note_tab__NOTE: |I|for further confirmation that the alarm is
unwarranted and must therefore be ignored, temporarily power even only
Software Not
in one of these sources and check that the alarm is no longer changed:|ii|
Compatible
• Vaux (24 VDC) -> K1 K2. For further details, consult page#s#20
• Ekip TT/Ekip T&P/EKIP Programming
If the conditions indicated above are not present, the software versions
between Mainboard and display (Ekip Touch) are not compatible with
each other: to restore compatibility, please contact ABB
CB status
CB state incorrect (esample: current present but CB in open state)
Switchboard Actor
Check configuration and connection of Ekip Link module
communication Error
Disconnection of Trip coil detected, check functionality
TC disconnected
Check Trip coil, status of the terminal and cables connecting to Ekip
Touch
Contact Wear
Make sure that the contacts/poles are in good condition.
IMPORTANT! Ignore the message if all the following conditions are
present at the same time:
• Vaux absence
• Absence of Ekip TT/Ekip T&P/Ekip Programming
• Presence of primary current near to self supply powering minimum
NOTE: modification of all parameters is inhibited via display; if
present, protections L, I and Iinst are active and function with the
parameters prior to the alarm (parameters of previous unit are active
if display has been replaced)
ABB | SACE Emax 2
Continued on the next page
Alarms or failures
2 - Self-diagnosis